Page 420 - Sustainable On-Site CHP Systems Design, Construction, and Operations
P. 420

CHWR CHWS
                       (Option)
                    15 Psig
                      Steam
                          water
                         Feed
                               FW
                           Exhaust
                                HEX
                                EXH-TO-HTHTF
                                      12-kV generator  3,520 kW
                                  SCR pump  350°F  CWS  *  1040-ton  360°F  CWR  2-stage  absorption HTHTF-To-steam HEX  chiller  310°F  HTHTF (hybrid heater)  pump  16 MMBtuh 930 GPM HTHTF-TO-HHW HEX  HWS  HWR  HTHTF  HTHTF-TO-DHW  HEX  DHWS  M  266°F  DHWR  Dump (high limit)  20 MMBtuh  * Optional with 600°F HTHTF
                                        Turbine
                                   149,600 LBM/h  835°F  Shaft  Combuster  42.7  MMBtu/h  heat exchanger  heating hot water high-temperature resistant heat  transfer fluid   hot water return  hot water supply  natural gas  outside air  selective catalytic reduction
                                        Compressor  3" NG  HEX  HHW  HTHTF  HWR  HWS  NG  OSA  SCR

                              Inlet  silencer  M

                                    Air  filter  480 V ES  160 psig  100-HP NG compressor (typ of 3)  1 backup  ICHP/CGS plant schematic.

                              45°F min temp  59°F DB  56°F WB  40°F  CHWR CHWS  55 tons  condenser water supply  condenser water return  chilled water supply  chilled water return  domestic hot water  domestic hot water return  domestic hot water supply


                               96°F DB  69°F WB  64°F  3"  15 psig  750 SCFM  950 Btu/CF  exhaust

                                  OSA  147,500  LBM/h  NG  Legend:  CWS  CWR  CHWS  CHWR  DHW  DHWR  DHWS  EXH  FIGURE 24-2




        392
   415   416   417   418   419   420   421   422   423   424   425