Page 87 - Uninterruptible Power Supplies
P. 87

Interconnecting the Standby and Normal Supplies
                                  Interconnecting the Standby and Normal Supplies  85


            High-Voltage Switchgear
            For high-voltage installations, the switchgear should comply with BS EN
            60298. The enclosures should protect the equipment against the ingress
            of solid foreign objects, and persons against touching hazardous parts, to
            one of the degrees of protection in BS EN 60529. (BS EN 60298 invokes
            BS EN 60694 which in turn invokes BS EN 60529).

            Prospective Fault Current Level
            For a set providing an alternative supply and not arranged to run in
            parallel with the normal supply, the prospective fault level will be
            the higher of the two supplies, which will almost certainly be that of the
            normal supply. For sets running in parallel with the normal supply,
            the prospective fault current will be the sum of the two fault cur-
            rents. The mechanical and thermal stresses imposed on the busbars
            are proportional to the square of the current, it follows that a modest
            additional current from a generator can have a significant effect
            within the switchboards.


            Information to Be Displayed at the
            Switchboard
            Single-Set Installations The generator panel of a single set, not
            intended to run in parallel with another set or the normal supply, is
            required by ISO8528 to display the following information:

              Voltage, with provision for indication of phase-to-phase and phase-
              to-neutral voltages
              Current, with provision for indication of each phase

              Other indications which should be considered includes:

              The frequency of the ac output
              Operating hours, that is, a cumulative hours-run counter
              For large sets only, indication of kW, kVAr, power factor, and cumu-
              lative kWh.

            Multiple-Set Installations Each generator panel of a multiple-set instal-
            lation not intended to run in parallel with the normal supply should
            display the following:

              Voltage, with provision for indication of phase-to-phase and phase-
              to-neutral voltages
              Current, with provision for indication of each phase
              kW indication for each set

         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   82   83   84   85   86   87   88   89   90   91   92