Page 85 - Uninterruptible Power Supplies
P. 85

Interconnecting the Standby and Normal Supplies
                                  Interconnecting the Standby and Normal Supplies  83


              In the previous paragraph the characteristics described as standard
            inverse, very inverse, and extremely inverse are the operating charac-
            teristics described in BS EN 60255. The characteristics are inverse
            with a definite minimum time and are known in full as inverse definite
            minimum time characteristics, sometimes abbreviated to IDMT.


            Protection of the Distribution System
            In a normal situation the overload relay characteristic of the supply
            would appear on the time grading graph to the right of and above the
            characteristics of the distribution system. Any fault on the distribution
            system would be cleared, enabling the healthy parts of the system to
            continue in operation. However, the prospective fault current obtain-
            able from the standby supply will be much less than that obtainable
            from the normal supply, and will probably be of the order of three times
            the rated current. On the protection time grading graph the effect is to
            move to the left, sometimes drastically, the supply characteristic. This
            characteristic may intersect some of the existing operating character-
            istics, thus lengthening their operating times or, worse, may leave
            them isolated in a high current section of the graph where the standby
            supply cannot operate.
              If the standby supply feeds a number of loads through dedicated
            changeover contactors or circuit breakers there should be no problem
            in providing protection because the distribution system is in effect
            duplicated. Where a small standby supply feeds a large distribution
            system and uses the same switchboard as the normal supply, it will be
            unlikely to be able to clear faults in the main distribution system and
            a cable fault near the power source may not be cleared, thus rendering
            the standby supply inoperative, until it can be restored by manual
            switching or repair. Such an event is unlikely and the risk may be
            acceptable; provided that the generator rating is large in relation to the
            final circuit protective devices, disconnection times complying with BS
            7671 should be achievable for the final circuits. The alternative is to
            connect the standby supply to a downstream point where the protection
            will be set at a lower level.


            Switchgear
            For the smaller and simpler generating sets, the switchgear may comprise
            a single molded-case circuit breaker mounted on the generating set base
            frame. For larger sets the switchgear is installed separately, and for mul-
            tiple-set installations the switchgear will comprise several cubicles with
            busbars and interconnecting wiring. Sometimes, such switchgear is
            installed in the engine room, but this is an extremely noisy location in



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   80   81   82   83   84   85   86   87   88   89   90