Page 82 - Uninterruptible Power Supplies
P. 82

Interconnecting the Standby and Normal Supplies
            80   Chapter Two


              delay is necessary. Downstream faults do not have any effect on the
              relay, hence the use of the word restricted in the name. The system
              requires four current transformers, one in the neutral which can
              be mounted in the terminal box or in the switchgear, and three cur-
              rent transformers in the phases which are usually mounted in the
              switchgear. The area protected lies between the three-phase current
              transformers and the neutral transformer. The system is applicable
              to sets of above say 100 kW. It is sometimes known as a balanced cur-
              rent system. Typical connections are indicated by Fig. 2.21.
            ■ Differential Current Protection. In this system the currents at the
              start and finish of each phase of the stator windings are compared. If
              any of the phases is not balanced, this indicates an internal fault and
              the generator should be deexcited and the engine shut down; since no
              discrimination with downstream protection is involved, no time
              delay is necessary. The system requires the three ends of the stator
              winding to be brought out of the stator and into the neutral terminal
              box and the installation of three current transformers in the box, the
              other three current transformers and the relays are usually mounted
              within the associated switchgear. This system is applicable to large
              sets, say above 1.5 MW. The area protected lies between the two sets
              of current transformers and for this reason the term unit protection
              is sometimes used. The term circulating current system is also some-
              times used. Typical connections are indicated by Fig. 2.22.
            ■ Standby Earth Fault Protection. This system is applicable to high-
              voltage generators which are resistance earthed. In this system the
              current flowing to earth from the star point is monitored and is
              applied to a relay. Any current flow indicates a fault and should oper-
              ate an inverse time-delayed trip. The system is unrestricted and the
              time delay is required to allow any downstream protection to operate.










                                          EF = Instantaneous earth
                                     EF
                                                  fault relay




            Figure 2.21  Typical connections to provide restricted earth fault
            protection.



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   77   78   79   80   81   82   83   84   85   86   87