Page 77 - Uninterruptible Power Supplies
P. 77

Interconnecting the Standby and Normal Supplies
                                  Interconnecting the Standby and Normal Supplies  75


            ■ It is not possible to use the standby supply independently unless the
              neutral contactor is closed.

              An alternative procedure is to install a reactor connected between the
            generator star point and the supply neutral. The reactor is to have suf-
            ficient reactance to limit the triplen harmonic current flow to within the
            limits set by ER G.5/4. This arrangement is discussed in ER G.59/1 and
            in ETR 113 but it is more complex and expensive than the preceding
            procedure and would seem to have limited application for single sets.

            Earthing Low-Voltage Supplies
            When the normal and standby supplies are running in parallel the neu-
            tral connection will usually be taken from the normal supply and,
            depending on the earthing arrangements and the agreement with the
            network operator, there may be a requirement for an earthing contac-
            tor or for an additional pole on the neutral contactor mentioned in an
            earlier paragraph. For multiple earthed systems, including PME, the
            neutral and earth connections are combined and a single pole neutral
            contactor is used. Figure 2.17 illustrates the electrical connections. For
            single-point earthed systems such as TN-S or TT an additional pole is
            required on the neutral contactor to avoid a second earth connection to
            the normal supply neutral. Figure 2.18 illustrates the electrical con-
            nections. If a separate earthing contactor is used, electrical interlocks,
            as required for the neutral contactor, must be provided.
              As was the case for the diagrams related to alternative connections,
            Figs. 2.17, 2.18, and 2.19 have been derived from diagrams appearing
            in ETR 113. Figure 2.17 provides a parallel path for the neutral cur-
            rent, the undesirable consequences of such an additional path have
            already been discussed at the end of the section titled “Neutral
            Connections for Single Sets Not Intended to Run in Parallel with the
            Normal Supply” in connection with Fig. 2.7.

            Earthing High-Voltage Supplies
            For high-voltage systems the network operator may use solid, resistor,
            reactor, or arc suppression coil earthing methods and a second earth-
            ing point will not normally be allowed. When a high-voltage standby
            supply is operating independently its star point must be connected to
            earth, usually through an earthing resistor, but when it is operating in
            parallel with the normal supply, the earth connection must be opened,
            for which purpose an earthing contactor is used. Figure 2.19 illustrates
            the electrical connections. With this arrangement the standby supply
            star point is not used and the system relies upon the normal supply for
            earthing.



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   72   73   74   75   76   77   78   79   80   81   82