Page 75 - Uninterruptible Power Supplies
P. 75

Interconnecting the Standby and Normal Supplies
                                  Interconnecting the Standby and Normal Supplies  73


            break, and for test runs it is similarly possible to transfer the essential
            load to the standby supply without a break, while leaving the nonessen-
            tial load connected to the normal supply. It should be noted that this
            advantage can only be gained if the normal supply circuit breaker con-
            nects to the section of busbar that supplies the nonessential load. (See
            Figs. 2.2 and 2.3.) These procedures require paralleling for short peri-
            ods only and the agreement with the network operator usually limits
            the duration to 5 min.
              The technical requirements are set out in Engineering Recommenda-
            tion G59/1 and its supporting document Engineering Technical Report
            113, both published by the Electricity Association.


            Features Required on the Generating Set
            The generating set should have been constructed with parallel running
            in mind. The coupling between the engine and alternator should be suf-
            ficiently robust to withstand an attempt to synchronize in phase oppo-
            sition without suffering damage; a shear pin is sometimes provided
            between the alternator and the coupling. The alternator poles should
            be provided with pole face damper windings to prevent phase swinging.
              As the set will be feeding into an infinite system the engine governor
            will have no control over the speed and the voltage regulator will have
            no control over the voltage. Instead the governor is used to control
            power (kW e ) and voltage regulator to control power factor (cos ). For
            synchronizing purposes the engine governor and the voltage regulator
            will require remote adjusting facilities.


            The Supply Authority’s Requirements
            For reasons connected with the safety of their operating and mainte-
            nance personnel the network operator will require electrical protection
            to ensure that their distribution network is not energized from the
            standby supply. For long-term continuous paralleling the protection
            required is complex but for the short-term occasional paralleling
            applicable to standby installations the protection required will usually
            consist of under- and overfrequency, under- and overvoltage, overcur-
            rent, earth leakage, and a 5-min timer, in addition the network opera-
            tor may require protection against neutral voltage displacement. The
            settings of the relays required for paralleling will be determined by the
            network operator.
              The purpose of the under- and overfrequency and voltage protection
            is to detect a loss of normal mains and to prevent the standby genera-
            tor back-feeding a part of the supply authority’s distribution system
            (islanding). The purpose of the neutral voltage displacement protection



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   70   71   72   73   74   75   76   77   78   79   80