Interconnecting the Standby and Normal Supplies
            70   Chapter Two






                                                  Alternator No 1








                                                  Alternator No 2







             Static balancer










                         R     Y    B     N    E
            Figure 2.14 Connecting the neutral for low-voltage multiple sets using a static balancer.


            ■ With the generator maker’s approval the generator neutrals are par-
              alleled. Unless the generators are identical and are working under
              identical conditions of excitation and loading there will be some third
              harmonic currents circulating in the neutrals.


            High-Voltage Installations
            The supply should be earthed through an earthing resistor as described
            for the single set installation but, for the reasons described in a forego-
            ing paragraph, it may not be advisable to connect together the star
            points of a multiple set installation. There are several methods of over-
            coming the difficulty, the matter should be agreed with the generator
            manufacturer:

            ■ Each machine is provided with an earthing contactor connected to a
              common earthing resistor but only one contactor is closed at any
              time.  A logic system ensures that one machine is earthed and