Interconnecting the Standby and Normal Supplies
70 Chapter Two
Alternator No 1
Alternator No 2
Static balancer
R Y B N E
Figure 2.14 Connecting the neutral for low-voltage multiple sets using a static balancer.
■ With the generator maker’s approval the generator neutrals are par-
alleled. Unless the generators are identical and are working under
identical conditions of excitation and loading there will be some third
harmonic currents circulating in the neutrals.
High-Voltage Installations
The supply should be earthed through an earthing resistor as described
for the single set installation but, for the reasons described in a forego-
ing paragraph, it may not be advisable to connect together the star
points of a multiple set installation. There are several methods of over-
coming the difficulty, the matter should be agreed with the generator
manufacturer:
■ Each machine is provided with an earthing contactor connected to a
common earthing resistor but only one contactor is closed at any
time. A logic system ensures that one machine is earthed and