Page 67 - Uninterruptible Power Supplies
P. 67
Interconnecting the Standby and Normal Supplies
Interconnecting the Standby and Normal Supplies 65
Generator Manual changeover or
circuit mechanically and electrically
Generator breaker interlocked devices
R
Y Normal
supply
B
N
E
(if provided)
Local
earth Essential Non-essential
electrode load load
Figure 2.8 Typical connections for alternative supplies when the normal supply
uses single point earthing (TN-S or TT).
Resistor
Neutral Earth busbar
busbar
Earth busbar
(a) (b)
Figure 2.9 Neutral earthing of a generator. (a) Low voltage. (b) High
voltage.
point will be connected to the earthing resistor which in turn will be con-
nected to the earth bar and on to the earth electrode (see Figure 2.9b).
High-voltage power is usually supplied from a three-wire system,
there being no neutral, an earth connection may not always be pro-
vided. For such installations triple pole electrically interlocked circuit
breakers will be required as illustrated by Fig. 2.10.
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.