Page 63 - Uninterruptible Power Supplies
P. 63

Interconnecting the Standby and Normal Supplies
                                  Interconnecting the Standby and Normal Supplies  61


              cally 5 min, and only for the purposes of maintaining continuity of
              supply while changing over from one source to the other.

              For standby power installations interest is limited to the alternative
            connection and to occasional paralleling. The document describes the
            technical requirements for earthing the standby supply, interconnect-
            ing the neutrals of the two supplies and the changeover devices, and
            the electrical protection required during parallel running. These mat-
            ters are discussed in the sections titled “Earthing the Neutral of the
            Standby Supply,” “Neutral Connections for Single Sets Not Intended to
            Run in Parallel with the Normal Supply,” and “Paralleling the Standby
            and Normal Supplies.”
              There is an associated guidance document Engineering Technical
            Report 113 (ETR 113) which discusses and describes these matters in
            detail. Many of the diagrams reproduced in this chapter have been
            derived from diagrams appearing in ETR 113.


            Earthing the Neutral of the Standby Supply
            It is important that the standby supply has a reliable earthing system;
            it is not safe to rely on any earthing arrangements that are not under
            the control of the site operating personnel. If the earthing system
            for the normal supply is local to the generating set and is under the
            control of the site operating personnel it may be permissible to use it
            as the earth for the standby supply. Figure 2.6 illustrates typical


                       Generator   Manual changeover or
                         circuit  mechanically and electrically
            Generator   breaker      interlocked devices
                                                              R

                                                              Y
                                                                 Normal
                                                                 supply
                                                              B
                                                              N





                                       Essential  Non-essential  Adjacent earth
                                        load       load      electrode
            Figure 2.6 Typical connections for alternative supplies when the normal supply
            is from an adjacent substation with its own local earth electrode.



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   58   59   60   61   62   63   64   65   66   67   68