Page 60 - Uninterruptible Power Supplies
P. 60

Interconnecting the Standby and Normal Supplies
            58   Chapter Two


              Operating regimes such as those described in the last two para-
            graphs should not be used indiscriminately, they require skilled and
            competent operating personnel who have the necessary experience and
            confidence to operate switchgear under the somewhat stressful condi-
            tions that always apply after a failure of the normal supply. For the
            benefit of operating personnel a wall chart should display relevant
            information such as that given above.


            The Generator Voltage
            Most standby generating sets are of a rating well below 1 MW and will be
            connected to systems using the standard final distribution voltage which,
            in the United Kingdom, is 400/230 volts. However generating sets having
            a rating approaching 1 MW may be associated with a high-voltage distri-
            bution system. In the United Kingdom, the predominant high-voltage
            distribution voltage is 11 kV, but 20kV is used in some rural areas.
              Each generator manufacturer will have determined a rating at
            which the transition from low voltage to high voltage occurs on grounds
            of costs and practicability. A generator designed for say, 100 kW at high
            voltage would comprise much insulation and very little copper; like-
            wise a generator designed for say 5 MVA at low voltage would comprise
            much copper and very little insulation. For every rating there is an
            optimum voltage but choice is usually limited to the standard distribu-
            tion voltages which in the United Kingdom are 400 V, 11 kV, and 20 kV.
            The precise rating at which the transition occurs depends on details of
            manufacturing techniques but it is likely to be of the order of 1250 kVA.
              The current rating of a 1250-kVA generator at 400 V is 1804 amperes
            and cables will be of large cross section and intractable and may be dif-
            ficult to install. If during the planning of an installation such difficul-
            ties are foreseen, it may be worth considering generating at low voltage
            and feeding directly into a step-up generator transformer. However,
            unless high voltage is already in use within the installation, its intro-
            duction is likely to cause problems with the competence of personnel
            and operating and safety procedures.


            The Electricity Supply Regulations 1988
            The Electricity Supply Regulations are currently applicable, within the
            United Kingdom, to suppliers of electricity, but they are soon to be
            replaced by the Electricity Safety, Quality and Continuity Regulations.
            These notes are included here as they indicate the underlying philoso-
            phy which seems unlikely to be changed by the new document.
              The Regulations set out the requirements for the distribution of elec-
            tricity, from its origin (a generating station or a substation) to the var-



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   55   56   57   58   59   60   61   62   63   64   65