Page 56 - Uninterruptible Power Supplies
P. 56

Interconnecting the Standby and Normal Supplies
            54   Chapter Two


            loss of supply both sets are started and the first available set supplies
            essential load 1, the second set is then paralleled and essential load 2
            is connected.

            Load Sharing
            When more than one set supplies the load, they will usually be of the
            same rating in which case they should share the kilowatt and kilovar
            loads equally. If they are of different ratings they should share the
            loads in proportion to their ratings.
              The simplest system of kilowatt load sharing is for the engine speed
            governors to allow a small drop in speed as the load increases as indi-
            cated by Fig. 2.4. The paralleled sets must of necessity run at the same
            speed and if each set has a similar load/speed characteristic, load shar-
            ing will automatically be achieved. If at some time the load sharing
            between two sets becomes unequal, both sets will be running at speeds
            which are not compatible with their load/speed characteristics and
            their governors will react to correct the errors.
              If the paralleled sets are of the different ratings, provided that the
            droop settings of each of the sets are the same, the load will be shared
            proportionally to their ratings. It can be seen from Fig. 2.4 that the load
            taken by any set can be increased or decreased by reducing or increas-
            ing the droop setting (the slope of the characteristic) or by altering the
            set speed (the vertical position of the characteristic).
              If the frequency droop is not acceptable, an alternative system of shar-
            ing the kilowatt loading is for the engine speed governors to be arranged
            for isochronous (constant speed) running. This requires electrical inter-
            connections between the governors to maintain load sharing.
              Kilovar load sharing between generators running in parallel is depen-
            dent upon the rotor excitation which in turn is determined by the volt-
            age regulators. As with kW load sharing the simplest system is for the


















            Figure 2.4 Kilowatt load sharing between two sets using a speed droop governor
            characteristic.


         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   51   52   53   54   55   56   57   58   59   60   61