Interconnecting the Standby and Normal Supplies
                                  Interconnecting the Standby and Normal Supplies  51


              closed contact of a load shedding relay. Aload shedding signal energizes
              the relay thus releasing the contactor which remains open until the
              load shedding signal is removed. A circuit breaker may be used in place
              of the contactor. For a large site using many load shedding relays and
              long runs of telephone type cable, consideration must be given to the
              relay operating current and the volt drop in the telephone-type cable.

              Figures 2.1 and 2.2 show typical methods of connecting single gener-
            ating sets, Fig. 2.1 applies to a small set using electrically and mechan-
            ically interlocked changeover contactors or circuit breakers, and Fig. 2.2
            applies to a set using electrically interlocked circuit breakers.



















            Figure 2.1 Single-line diagram showing a typical method of connect-
            ing a small single set using changeover contactors.
























            Figure 2.2 Single-line diagram and switching status
            table showing a typical method of connecting a single set
            using electrically interlocked circuit breakers.