Page 57 - Uninterruptible Power Supplies
P. 57

Interconnecting the Standby and Normal Supplies
                                  Interconnecting the Standby and Normal Supplies  55


            voltage regulators to introduce a small drop in terminal voltage as the
            kilovar load increases as indicated by Fig. 2.5. The difference between
            Figs. 2.4 and 2.5 is that in the former the axes represent speed and kW
            loading, and in the latter they represent voltage and kVAr loading. As
            the paralleled sets will be running at the same voltage, if they have the
            same droop settings, load sharing will be achieved automatically. One
            method of achieving the droop is for each regulator to be provided with
            a signal from a quadrature drop current transformer connected in one
            phase of its generator output. The quadrature drop signal is added to
            the terminal voltage sampled by the voltage regulator and thereby
            introduces a voltage droop.
              If the voltage droop is not acceptable, an alternative system of shar-
            ing the kilovar loading is used, this requires interconnections between
            the voltage regulators and maintains constant voltage. If one machine
            is taking too great a share of kilovars the sharing signal will cause its
            regulator to reduce its excitation.
              Where frequency and voltage droop are used to share load and kVAr
            the droop will be, say, 3 or 4 percent and it is usual to arrange for the
            nominal frequency and voltage to be achieved at normal running load.


            Interconnections with the Normal Supply
            The main power interconnections between the normal supply, the
            standby supply, and the essential and nonessential loads depend on the
            number of sets in use and whether the power changeover is performed
            with two circuit breakers or an arrangement of contactors. Where the
            normal and standby supplies are required to be paralleled, the follow-
            ing comments are applicable but the reader should in addition refer to
            the section titled “Paralleling the Standby and Normal Supplies.”




















            Figure 2.5 Kilovar load sharing between two sets using a voltage regulator with a quad-
            rature droop characteristic.


         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   52   53   54   55   56   57   58   59   60   61   62