Page 66 - Uninterruptible Power Supplies
P. 66

Interconnecting the Standby and Normal Supplies
            64   Chapter Two


                      Generator    Manual changeover or
                        circuit  mechanically and electrically
            Generator  breaker      interlocked devices

                                                              R
                                                              Y   PME
                                                                 Normal
                                                              B  supply

                                                              N & E






                              Local
                              earth    Essential  Non-essential
                            electrode    load      load
            Figure 2.7 Typical connections for alternative supplies when the normal supply
            uses multiple earthing (PME, TN-C-S, or TN-C).


              will be required to select one supply or the other as illustrated by
              Fig. 2.8. The fourth pole is required to avoid earthing the neutral at
              a second point.
            ■ TT systems in which the neutral is earthed at the power source but the
              network operator does not provide an earthed protective conductor.
              Where a standby supply is installed in such a system a four-pole
              changeover device will be required (Fig. 2.8). The fourth pole is required
              to avoid earthing the neutral at a second point.

            Figures 2.6, 2.7, and 2.8 have been derived from diagrams appearing
            in ETR113. It will be noted that Fig. 2.7 provides a parallel path for
            the neutral current, which may have undesirable consequences. One
            path uses the neutral conductor but there is another path which uses
            the protective conductors connecting to the local earth. The current
            in the protective conductors will be indeterminate, it may exceed the
            rating of the protective conductor and may upset the current balance
            in any protective residual current devices. The difficulty can be over-
            come by using four-pole changeover devices.



            High-Voltage Installations
            In a single set high-voltage installation the generator will usually be
            connected, as a three-wire machine, to a distribution board. The star



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   61   62   63   64   65   66   67   68   69   70   71