Page 68 - Uninterruptible Power Supplies
P. 68

Interconnecting the Standby and Normal Supplies
            66   Chapter Two


             Standby    Electrically interlocked  Supply Authority's
             generator       circuit breakers    circuit breaker
                    Standby supply  Normal supply
                                                                   R

                                                                   Y  Normal
                                                                     supply
                                                                   B

                                                                   E
                                                               (if provided)
            Earthing
            resistor

                             Essential  Non-essential
                             load       load


            Figure 2.10 Typical connections for alternative supplies at high voltage.

            Neutral Connections for Multiple Sets
            Not Intended to Run in Parallel with the
            Normal Supply
            Running Generators in Parallel- and
            Triplen-Current Flow
            Triplen currents have not been previously mentioned and it is appro-
            priate to introduce them here. The harmonic orders 3, 6, 9, 12, etc. are
            known as triplen harmonics or triplens. They have zero-phase sequence
            and triplen currents flowing in the phase conductors become additive in
            the neutral, hence the concern expressed in the following text.
              The voltage generated by a loaded salient pole generator will include
            a third harmonic and other triplen components the magnitude of which
            will be dependent upon the machine design, its excitation, and its load-
            ing. If the machines are identical and are equally loaded and excited
            the triplen harmonic voltages in each of the machines will be equal, in
            phase and balanced and there will be no resulting current flow. If the
            machines are not identical or are not equally loaded or excited, triplen
            harmonic currents will circulate between the machines as shown in
            Fig. 2.11. Any triplen load currents taken from them will similarly be
            additive in the neutral busbar return path as shown in Fig. 2.12.
              It is likely that both the above conditions will exist at the same
            time and for the triplen currents in the neutral connections to be
            unexpectedly large. When salient pole generators are to be run in
            parallel, consideration should be given to the possibility of undesir-
            able third harmonic currents circulating in the neutral connections
            of the machines. If the neutrals of paralleled generators are not


         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   63   64   65   66   67   68   69   70   71   72   73