Page 80 - Uninterruptible Power Supplies
P. 80
Interconnecting the Standby and Normal Supplies
78 Chapter Two
Standby Essential load Supply Authority's
generator circuit breakers circuit breaker
Standby supply Normal supply
CB1 CB2
R
Y Normal
supply
B
E
Earthing (if provided)
contactor
EC
Earthing
resistor
Essential Non-essential
load load
Local
earth
electrode
Device CB1 CB2 EC
Essential load from O I O
normal supply
Essential load from
standby supply I O I
The two supplies I I O
in parallel
Synchronizing facilities are provided across each of the essential load circuit breakers.
Figure 2.19 Typical connections and switching status table for high voltage parallel running.
a pilot exciter with permanent magnet excitation (see Fig. 1.4).
Alternatively, instead of a pilot exciter, power may be derived from
the generator output terminals (see Figure 1.5); with this arrange-
ment, under short circuit conditions, there will be a loss of exciter
field unless a system to maintain it is included. One system uses
current transformers to maintain excitation during a fault. Another
system derives power from a dedicated third harmonic winding in
the stator.
The steady-state short circuit current available from an ac generator
is normally of the order of three times the rated current.
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.