Page 80 - Uninterruptible Power Supplies
P. 80

Interconnecting the Standby and Normal Supplies
            78   Chapter Two


            Standby           Essential load           Supply Authority's
            generator         circuit breakers         circuit breaker
                     Standby supply   Normal supply
                         CB1             CB2
                                                                   R

                                                                   Y    Normal
                                                                        supply
                                                                   B
                                                                     E
            Earthing                                             (if provided)
            contactor
            EC

            Earthing
            resistor
                                Essential      Non-essential
                                load           load
                    Local
                    earth
                    electrode

                       Device           CB1       CB2     EC
                       Essential load from  O      I       O
                       normal supply
                       Essential load from
                       standby supply     I       O        I
                       The two supplies   I        I       O
                       in parallel


              Synchronizing facilities are provided across each of the essential load circuit breakers.
            Figure 2.19 Typical connections and switching status table for high voltage parallel running.


            a pilot exciter with permanent magnet excitation (see Fig. 1.4).
            Alternatively, instead of a pilot exciter, power may be derived from
            the generator output terminals (see Figure 1.5); with this arrange-
            ment, under short circuit conditions, there will be a loss of exciter
            field unless a system to maintain it is included. One system uses
            current transformers to maintain excitation during a fault. Another
            system derives power from a dedicated third harmonic winding in
            the stator.
              The steady-state short circuit current available from an ac generator
            is normally of the order of three times the rated current.



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   75   76   77   78   79   80   81   82   83   84   85