Page 244 - Wastewater Solids Incineration Systems
P. 244
206 Wastewater Solids Incineration Systems
TABLE 9.2 Summary of regulatory requirements for incinerators.
Regulation Continuous monitoring system description/requirement
40 CFR Part 60 Subpart O for Instruments for the following:
Sections 60.150 through 60.156 • 60.153 (a): Mass/volume sludge charged
• 60.153(b)(1): Pressure (differential pressure) for scrubber(s)
• 60.153(b)(2): Oxygen analyzer for flue gas
• 60.153(b)(3): Temperature (thermocouple) for all hearths
• 60.153(b)(4): Flow auxiliary fuel
40 CFR Part 60 Section 60.152 Analyzer for the following:
Standard for Particulate Matter • 60.152(a)(2): COMS
(Opacity) 60.11(b) and 60.11(e)(5) • 60.11: COMS
Compliance with standards and • 60.13 (a): COMS
maintenance requirements, and • Continuous opacity measurement systems are optional under
60.13 (Monitoring) 40 CFR 60 Subpart O. If used, they must meet the following
standards:
40 CFR 60 App A, Method 9 Visual Determination of the
Opacity of Emissions from Stationary Sources
40 CFR 60 App B, Performance Specification 1—COMS
40 CFR 60 App F—Quality Assurance Requirements for Gas
Continuous Emission Monitoring Systems Used for
Compliance Determination
40 CFR 503.40 Applicability, Analyzers for the following:
40 CFR 503.44 Operational • 503.40: carbon monoxide (CO)
Standard Total Hydrocarbons and • 503.44(a), 503.45(c): moisture
40 CFR 503.45 Management • 503.44(b), 503.45(b): oxygen
Practices • 503.44(c), 503.45(a): total hydrocarbons
Reference:
40 CFR 60 App B, Performance Specification (PS)
• Performance Specification 3—O , CO
2 2
• Performance Specification 4, 4b, CO, O
2
• Performance Specification 8, 8A volatile organic
compounds, THC
• 40 CFR 60 App F—Quality Assurance Requirements for
Gas Continuous Emission Monitoring Systems Used for
Compliance Determination
(Also please refer to 503.41 Special Definitions)