Page 334 -
P. 334

11.14                     CHAPTER ELEVEN

                                                       C: 300% controlled
           100
              -  -  ~  ~   ~  .  .  .   ~  ~   ~       recycle
                            ~  A
              _    ~  No sludge------~   ~  :  ,   "~   NN~  D: COntact clarifier
                         /
            80
            70
                   recycle control   ~         ~
            60
            50
            40
              -         B: 25% controlled-'f \   \   \       \
            30
            20
         g.  10

            0.2  .3  .4.5.6.7  1.0  1.52.0  3  4  5  6
                                              10  15  20  30  4050   100  150
                           Nominal micrometer diameter log scale
         FIGURE  11.4  Particle size distribution comparison.

         cium carbonate crystals. The depth and density of the residuals in the basin can be con-
         trolled by wasting residuals and by the degree of recirculation. The mixing and recircu-
         lation zone is separated from the sedimentation zone by a conical baffle wall within the
         basin. An example of a  solids contact unit is shown in Figure  11.5.
           Effective solids contact units pull settled residuals from near the floor at the center of
         the basin with a large-diameter turbine or impeller and recirculate the residuals at a high
         rate with the water entering the basin. The maximum recirculation rate is typically 10 to
         1 based on incoming flow. The mixer is provided with a variable-speed drive for adjust-
         ing the recirculation rate to meet treatment conditions.
           Where multiple solids contact units are installed, small recirculation pumps, operated
         to recirculate solids from one unit to another, are often used during start-up of a unit that
         has been out of service for cleaning. This is especially helpful during periods of low wa-
         ter temperature.
           Side  water  depth  of  solids  contact  basins  usually  varies  from  14  to  18  ft  (4.3  to
         5.5 m) and depends on basin size and the equipment manufacturer's requirements. Con-
         tact time in the mixing zone is typically 15 to 30 min, measured by the volume of water
         within and directly under the baffle wall.
           Surface loading rate in the sedimentation zone is generally measured 2 ft (0.6 m) be-
         low  the  water surface,  based  on the  surface area between  the baffle wall and the basin
         wall. Surface loading rates are usually in the range of 1.0 to  1.75 gpm/ft 2 (2.4 to 4.3 m/h).
         Where coagulation for turbidity removal is required, surface loading rates are generally
         in  the  lower end  of this  range  or  less.  Where  possible, design  requirements  should be
        based on successful plants using the same or similar source water.
           For the straight lime and lime-soda ash process, residuals are composed primarily of
        heavy calcium carbonate crystals without the more gelatinous and lighter magnesium hy-
        droxide component.  The  heavy calcium carbonate  crystals create  some difficulty in re-
        circulating residuals. In any case, the manufacturer should be advised of the nature of the
        process so that the basin design will function properly. Equipment specifications should
        establish a minimum percentage of solids to be maintained in the mixing zone. A mini-
   329   330   331   332   333   334   335   336   337   338   339