Page 112 - Advanced Design Examples of Seismic Retrofit of Structures
P. 112

104   Advanced Design Examples of Seismic Retrofit of Structures
















             (A)                              (B)















              (C)                             (D)














                                (E)
            FIG. 2.54 Progression of the retrofit project on the example building. (A) The building before
            retrofit. (B) Finalized reinforcement installation. (C) Spraying concrete. (D) Finalized concrete
            spray. (E) Implementation of the walls finishing. (Permission from DRES.)


                                               t m
                              E eq ¼ 0:623  0:070  +1:10 E c           (2.42)
                                               t c

                                               t m
                              G eq ¼ 0:190  0:062  +1:06 E c           (2.43)
                                                t c
            2.8.4.3 Acceptance Criteria
            Typically, the shotcrete overlay is assumed to resist all the lateral force applied
            to a retrofitted wall with the brick masonry being neglected altogether [18].