142   Advanced Design Examples of Seismic Retrofit of Structures


                   0.40
                 Distance of building center of rigidity and center of mass, %  0.30
                   0.35


                   0.25

                   0.20
                   0.15

                   0.10
                   0.05
                   0.00
                      STORY9  STORY8  STORY7  STORY6  STORY5  STORY4  STORY3  STORY2  STORY1  STORY0  STORY-1 STORY-2
                Integrated-DX  0.15  0.16  0.17  0.17  0.18  0.18  0.16  0.13  0.07  0.08  0.13  0.08
                South-DX  0.15  0.22  0.17  0.16  0.16  0.15  0.13  0.11  0.03  0.14  0.19  0.13
                North-DX  0.09  0.17  0.18  0.18  0.18  0.18  0.17  0.13  0.09  0.21  0.36  0.17
               (A)
                   0.40
                  Distance of building center of rigidity and center of mass, %  0.30
                   0.35


                   0.25
                   0.20

                   0.15
                   0.10
                   0.05

                   0.00
                      STORY9  STORY8  STORY7  STORY6  STORY5  STORY4  STORY3  STORY2  STORY1  STORY0 STORY-1 STORY-2
                Integrated-DY  0.07  0.06  0.05  0.07  0.16  0.19  0.18  0.18  0.18  0.14  0.09  0.09
                South-DY  0.05  0.08  0.24  0.24  0.37  0.38  0.37  0.35  0.32  0.16  0.05  0.02
                North-DY  0.20  0.05  0.08  0.13  0.18  0.22  0.24  0.23  0.28  0.28  0.13  0.15
               (B)
            FIG. 3.16 Distance of center of mass and center of rigidity in each story. (A) X-direction.
            (B) Y-direction.


            – development of “resisting cores” in the most favorable locations of the
               building in accordance with the architectural concerns in order to minimize
               the CoM-CoR eccentricity and irregularity, increasing the stability, ensur-
               ing proper stiffness distribution, and increasing the resistance of the build-
               ing. In the next stage, the possible retrofit solutions are studied and the
               best method is selected based on technical, economical, and feasibility
               considerations.