Page 224 - Advanced Design Examples of Seismic Retrofit of Structures
P. 224

Example of a Steel Frame Building With Masonry Infill Walls Chapter  4 217


                       KL                               s ffiffiffiffiffiffiffiffiffiffi
                                                             2
                        r                          2      2π E   6440
                    β ¼   ,F:S: ¼ 1:67 + 0:375β 0:125β ,C c ¼  ¼ p ffiffiffiffiffi
                        C c                                 F y    F y
                                                2
                             KL              12π E   105 10 5
                            if  > C c ! F a ¼
                                                  2
                              r                KL   ¼   KL   2
                                           23
                                               r         r
             where:
                P CL ¼lower-bound compression strength of the column;
                A ¼column cross-sectional area;
                K ¼effective length factor determined in accordance with AISC [12];
                L¼laterally unbraced length of the member; and
                r ¼governing radius of gyration.
             The lower-bound axial strength of all the column sections in the example build-
             ing is presented in Table 4.5. The lower-bound flexural strength of all the col-
             umn sections in the example building which is presented in Table 4.6 is
             determined based on the method in Section “Flexural and Shear Strength of
             Columns,” except for replacing F yL as the lower-bound yield strength of the
             material with F yE .

             4.4.2.3  The Retrofit Solution
             As previously stated, because of the high length of the walls in longitudinal direc-
             tion, these walls cannot be regarded as infill walls; therefore, the building is seis-
             micallyvulnerable.However,thewallsintransversedirectioncanprovidestiffness
             and strength to the building because they meet the requirement for infill panels.
             Based on these results, the following retrofit solution for the building is proposed:
             l Longitudinal direction: inclusion of concentric steel braces to the building.
             l Transverse direction: considering the existing infill panels as the lateral
                load-bearing system; if not adequate, retrofitting these panels with shotcret-
                ing is considered.
             In this example, only the retrofit of the building in a transverse direction which
             is related to the retrofit of infill walls is presented. The retrofit design process of
             adding concentric steel braces to the building, which is recommended for this
             example building in the longitudinal direction, is presented in a separate exam-
             ple in Chapter 5.

             4.4.2.4  Modeling of the Building
             For modeling of the building, ETABS is used. It is assumed that the example
             building is located in an area with very high seismicity with the design PGA
             of 0.35g according to Iranian Code of Practice for Seismic Resistant Design
             of Buildings (Standard 2800) [13]. The soil condition is III according to
   219   220   221   222   223   224   225   226   227   228   229