232 Advanced Design Examples of Seismic Retrofit of Structures


            For buildings with flexible diaphragms, each line of framing shall be indepen-
            dently evaluated.
               Torsional Strength. A torsional strength irregularity shall be considered to
            exist in any story if the diaphragm above the story under consideration is not
            flexible and, for a given direction, the ratio of the critical element DCRs for
            primary elements on one side of the center of resistance of a story, to those
            on the other side of the center of resistance of the story, exceeds 1.5.
               In the example building, there is no in-plane or out-of-plane discontinuity.
            Because of the similar number of components in the stories and their similar
            section profiles, the difference of the ratio of the average shear DCR of any story
            and that of an adjacent story in the same direction is less than 25%. In addition,
            the building has no torsional strength irregularities.
               The Fundamental Period of the Building, T, Is Greater Than or Equal to 3.5
            Times T s ; The natural period of the example building is 0.346 sec according to
            Section “Natural Period of the Building,” which does not exceed
            3.5 0.7¼2.45 s.
               The Ratio of the horizontal dimension at any story to the corresponding
            dimension at an adjacent story exceeds 1.4 (excluding penthouses); There is
            no major difference in the horizontal dimensions of the stories in the example
            building.
               The building has a torsional stiffness irregularity in any story. A torsional
            stiffness irregularity exists in a story if the diaphragm above the story under con-
            sideration is not flexible and the results of the analysis indicate that the drift
            along any side of the structure is more than 150% of the average story drift;
            As Table 4.11 shows, the example building has no torsional stiffness irregular-
            ity in any story.
               The building has a vertical stiffness irregularity. A vertical stiffness irreg-
            ularity exists where the average drift in any story (except penthouses) is more
            than 150% of that of the story above or below; According to the results pre-
            sented in Table 4.11, the example building has no vertical stiffness irregularity.
               The building has a non-orthogonal lateral-force-resisting system; As the
            lateral-force-resisting system, the example building has concentric braces in
            the longitudinal direction (which is assumed to have already been added to
            the building) and the infill panels in the transverse direction.
               In conclusion, the example building can be analyzed by the linear static
            procedure.



            4.4.2.6 Evaluation of the Building
            Actions Calculations
            Deformation-Controlled Based on Code 360 [10], deformation-controlled
            actions for the LSP denoted by Q UD shall be calculated in accordance with
            Eq. (4.26):

                                      Q UD ¼ Q G + Q E                 (4.26)