236 Advanced Design Examples of Seismic Retrofit of Structures


            The Results
            The results of evaluation of infill panels under the deformation-controlled
            actions according to Section “Deformation-Controlled” are shown in
            Table 4.13. As can be seen, none of the infill panels meets the acceptance cri-
            teria as set out in Section “Deformation-Controlled,” and hence all of them
            should be considered for retrofit. As an example, calculations for infill panel
            A-1-3 in the floor story are presented. It is noted that in calculation of the
            expected capacity of the bare frame (V fre ), only the sum of the shear capacity
            of the columns in this frame is considered.
               h inf ¼280 cm, L inf ¼540 cm, t inf ¼20 cm, a¼31 cm
                                               280
                        θ ¼ tan  1  h inf  ¼ tan  1  ¼ 27:41degrees
                                 L inf        540
                                                           2  9
                   Left column : 2UNP22PL24 1 ! A s ¼ 41:57 cm =
                                                              ! A s min
                   Right column : 2UNP18PL24 1 ! A s ¼ 32:77cm 2 ;
                                                           2
                                                  ¼ 32:77cm and C v ¼ 1:0
               f m ¼5 MPa, F y ¼240 MPa
                         a t inf  f me   cosθ  31 20 50  cos 27:41Þ
                                                          ð
              V inf ¼ Q CE ¼             ¼                      ¼ 11;008 kg
                               2:5                  2:5
                     V fre ¼ 0:6F y A s C v ¼ 0:6 2400 32:77 1:0 ¼ 47;189 kg
                   8
                        V fre  47,189
                     β ¼    ¼       ¼ 4:287
                   >
                   >
                   <          11,008
                        V inf
                                           ! based onTable 4:12 : m ¼ 6:07
                            L inf  540
                   >
                               ¼
                   >                 ¼ 1:93
                   :
                            h inf  280
               Table 4.14 shows the checking of the compact section of the columns of the
            example building. In addition, the results of evaluation of the columns under
            displacement-controlled and force-controlled actions are presented in
            Table 4.15.
               According to ASCE 41 [1], the acceptance criteria of steel columns under
            combined axial compression and bending stress, where the axial column load
            is less than 50% of the lower-bound axial column strength, P CL , the column
            shall be considered deformation-controlled for flexural behavior and force-
            controlled for compressive behavior and the combined strength shall be evalu-
            ated by Eq. (4.32) or (4.33).
                                            P UF
                                    For 0:2      0:5
                                            P CL
                                   8                                   (4.32)
                              P UF     M x      M y
                                  +         +           1:0
                              P CL  9 m x M CEx  m y M CEy