Example of a Steel Frame Building With Masonry Infill Walls Chapter  4 267


                                A ¼ 4 2 30 0:8 ¼ 192cm  2
                                        0:8 30 3          4
                              I ¼ 4 2          ¼ 14;400 cm
                                          12
                                        6740      kg
                                     f v ¼   ¼ 35
                                         192     cm 2
                                   6740 61:4 15        kg
                               f b ¼             ¼ 431
                                       14,400         cm 2
                               q ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
                                          p ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi  kg
                                   2   2      2    2
                            f r ¼  f v + f b ¼  35 + 431 ¼ 433  2
                                                          cm
             where:
                A ¼weld area;
                I ¼moment of inertia of the weld line about the axis of flexure;
                f v ¼shear stress;
                f b ¼bending stress; and
                f r ¼resultant stress.
             Based on the Iranian National Building Code; Part 10: Steel Buildings [23], the
             allowable stress of the weld is 0.3 ϕF ue . The inspection is made by a licensed
             inspector on the fabrication site and hence ϕ ¼0.75. It is assumed that E60 elec-
             trode is used, and hence F ue ¼420MPa.
                                                            kg
                          F vw ¼ 0:3ϕF ue ¼ 0:3 0:75 4200 ¼ 945
                                                            cm 2
                           f r  433             a e   0:46
                      a e ¼  ¼     ¼ 0:46 ! a w ¼   ¼     ¼ 0:65cm
                          F vw  945            0:707  0:707
             where a e ¼effective weld throat and a w ¼weld throat.
                Consequently, four triangular plates with the length of 30cm and thickness
             of 1cm on each side of the connections can be considered as stiffeners to the
             corner plates. The retrofit details of the cradle-type connections are shown in
             Fig. 4.24. More information about the retrofitting of cradle-type connections
             can be found in Moghaddam [16] and Code 360 [10].



             4.5 ISOLATION OF INFILL WALLS NOT MEETING INFILL
             PANEL REQUIREMENTS FROM THE FRAME

             In some case where the walls cannot meet the minimum requirements of infill
             walls, or it is intended to exclude the infill wall from contributing to the load-
             bearing mechanism because of excessive demands on the frame members or the
             imposed irregularity on the building, isolation of the infill from the surrounding
             frame can be considered as an option. The design procedure of the isolation sys-
             tem should lead to guaranteeing isolation of the wall from the frame in the