Page 463 - Air pollution and greenhouse gases from basic concepts to engineering applications for air emission control
P. 463

444                                               14  Indoor Air Quality

              The plot over time is shown in Fig. 14.4.

              In addition to the analytical models above, there are a variety of computation
            fluid dynamics (CFD) models that can be employed for the predication of indoor air
            quality and indoor air pollutant concentrations. Readers are recommended to learn
            these specialized models from other publications including those listed in the
            Reference section [10–20].



            14.5 Practice Problems


            1. Minimum ventilation requirement is the __________ value of the ventilation
              requirements based on sensible heat balance, moisture balance, and pollutant
              balance.
               a. maximum
               b. minimum
               c. average
               d. arbitrary
            2. While you were cooking using gas burners in your kitchen, the measured
              concentrations of CO and CO 2 were 10 and 3500 ppmv, respectively. Is the air
              quality in your cooking environment acceptable based on these two pollutants
              only? (Given: the TLV’s for CO and CO 2 are 25 and 5000 ppmv, respectively).

               a. Yes, because the CO concentration is below the corresponding TLV.
               b. No, because the CO 2 concentration is below the corresponding TLV.
               c. Yes, because the normalized TLV is below unit.
               d. No, because the normalized TLV is above unit.
            3. In a Class 1 clean room, the measured total particle concentration is 9 particles/
                3
                                                         3
              m for particles larger than 0.1 μm and 3 particle/m for particles larger than
              0.2 μm. Does this cleanroom meet the Class 1 criteria?
                                                           3
            4. In a large auditorium with a ventilation rate of 6 m /s, the carbon dioxide
              concentrations in the exhaust air and supply air are 800 and 400 ppmv,
              respectively. The specific volume of exhaust and supply air are 0.82 and
                    3
                                                                             3
              0.78 m /kg dry air, respectively. The building has an air volume of 8,000 m ,
              and the air inside is assumed to be completely mixed. In a power failure, all
              exhaust fans are stopped, and there are 1000 people inside, each generates a heat
              of 200 W. Assume there is no air exchange between the inside and outside of the
              auditorium. How long it will take the CO 2 to reach the ceiling threshold value of
              5,000 ppmv after the power failure.
            5. There are 30 students in a classroom, each student produce 120 W of sensible
              heat and 100 g of water vapour per hour (or 70 W latent heat). The room air
              temperature is 20 °C and the specific volume and a relative humidity of 50 %.
   458   459   460   461   462   463   464   465   466   467   468