Page 299 - Alternative Energy Systems in Building Design
P. 299

BETZ’ LAW OF FLUID DYNAMICS  273


                         The graph in the figure represents the plot of the preceding equation, where the hori-
                       zontal axis reflects the ratio v /v , and the vertical axis is the coefficient of performance
                                                 1
                                               2
                       C . By differentiating E &  with respect to v /v for a given fluid speed, v , and a given area
                        p
                                                                                1
                                                        2
                                                          2
                       S, we can find the maximum or minimum value for E &  . The result is that  E &  reaches max-
                       imum value when v /v = 1/3 or, simply stated, outgoing velocity equals one-third of the
                                         2
                                       2
                       incoming liquid or air velocity.
                         Substituting the v /v ratios in the preceding formula with 1/3 results in
                                          2
                                        2
                                                         16  1      3
                                                   P   =    ×  × ρ Sv
                                                    max            1
                                                         27  2
                       Therefore, the work rate obtainable from fluid flow with area S and velocity v is
                                                                                        1
                                                           1
                                                       P = ρ Sv 3
                                                           2   1
                       In electrical engineering, the coefficient of performance is defined as the ratio of the
                       power output of a generator divided by the maximum power. In the case of wind tur-
                       bines, the coefficient of performance C equals P/P max  and has a maximum value of
                                                       p

                                               C p,max  =  16  =  . 0 593 , or 59.3%
                                                      27

                       It should be noted that coefficients of performance in general are expressed as a deci-
                       mal and not as a percentage.
                         Significant losses of power in wind energy turbines are attributed to a number of
                       factors, such as rotor bearing friction, heat or copper loss, and air friction losses. In
                       general, the C value of modern turbines used in windmills ranges from 0.4 to 0.5, which
                                  p
                       represents about 70–80 percent of the theoretically possible limit. Figure 8.3 illustrates
                       the atmospheric air convection cycle.



















                        Figure 8.3  Graphic representation of wind kinetic energy
                        at work.
   294   295   296   297   298   299   300   301   302   303   304