Example 8.4



                    Using Figure 8.4, calculate the relative costs of providing refrigeration at 5°C, –20°C, and –50°C. From
                    the figure, the ordinate values are given as follows.











                    Therefore,  compared  with  cooling  at  5°C,  cooling  to  –20°C  is  0.257/0.144  times  as  expensive,  and
                    cooling  to  –50°C  is  0.426/0.144  times  as  expensive.  This  analysis  assumes  that  the  two  refrigeration
                    systems operate equally efficiently with respect to the reversible limit and that the major cost is the power
                    to run the compressors.


                    In Example 8.5, a real refrigeration system is considered and operating costs are estimated.


                    Example 8.5


                    Obtain a cost estimate for a refrigerated cooling utility operating at 5°C.


                    Consider a single-stage refrigeration system to provide refrigeration at 5°C, using 1,1 difluoroethane (R-
                    152a) as the refrigerant. The process flow diagram and operating conditions are given in Figure E8.5 and
                    Table E8.5, respectively.


                    Figure E8.5 Process Flow Diagram for Simple Refrigeration Cycle of Example 8.5