Page 106 - Applied Process Design For Chemical And Petrochemical Plants Volume III
P. 106

66131_Ludwig_CH10C  5/30/2001 4:21 PM  Page 74










                       74                        Applied Process Design for Chemical and Petrochemical Plants

                            Example 10-5. Calculation of Weighted MTD 59     except in those cases when heat losses to the atmosphere or
                                                                             other outside medium are either known or planned.
                         A gas is to be cooled from 190°F to 105°F with partial con-  Plant 130  presented a technique for comparative heat
                       densation taking place. The dew point is 120°F. The cooling  exchange performance evaluation that is based on his effi-
                       water enters at 90°F and leaves at 110°F. Figure 10-37 illus-  ciency method and can include almost any style and appli-
                       trates the basic exchanger functions.                 cation of exchanger.
                                                                               In condensers where heat loss is desired, insulation
                         1. The heat load is                                 often is omitted from piping carrying hot fluids to take
                                                                             advantage of the heat loss to the atmosphere. In any heat
                        Q (Desuperheat)  =  420,000 Btu/hr                   exchange equipment the heat released or lost by one fluid
                       Q (Condensation) =  1,260,000 Btu/hr                  must be accounted for in an equivalent gain by a second
                                                                             fluid, provided that heat losses are negligible or otherwise
                                        1,680,000 Btu/hr
                                                                             considered.
                         2. The cooling water temperature rise in each zone is
                                                                             Heat Load or Duty
                       Desuperheating:   T, °F  = (110 – 90) (420,000)/1,680,000
                                                                               The heat load on an exchanger is usually determined by
                                          = 5°F
                                                                             the process service conditions. For example, the load on a
                        Condensation:   T, °F  = (110 – 90) (1,260,000)/1,680,000
                                                                             condenser for vapors from a distillation column is deter-
                                          = 15°F
                                                                             mined by the quantity and latent heat of vaporization at the
                                                                             condensing conditions, or for gas coolers, by the flow of gas
                         3. For desuperheating, the LMTD is
                                                                             and the temperature range required for the cooling.
                       190 → 120
                                                                               For sensible heat changes:
                       110 ← 90
                        80        15                                         q     W c p  1t 2      t 1 2                 (10-18)
                       Reading Figure 10-33:                                   For latent heat changes:
                       LMTD   38.8°F
                                                                                                                          (10-19)
                                                                             q     W l v
                         4. For condensation, the LMTD is
                                                                               For cooling (or heating) and latent heat change (con-
                       120 → 105                                             dense or boil):
                       105 ← 90
                                                                                                                          (10-20)
                                                                             Q     q'     Wc p  1t 2      t 1 2     Wl v
                        15        15
                       LMTD = 15°F                                             An item of heat exchange equipment can be used for any
                                                                             of these heat changes, or any combination of them, pro-
                         5. The weighted LMTD for calculations is            vided the loads are established to correspond with the phys-
                                                                             ical and thermal changes actually occurring or expected to
                                           Q total
                       Wt. LMTD                                              occur in the unit. Thus, the heat load must be known for the
                                     Q des      Q cond
                                                                             design of an exchanger, although it may be determined on
                                                                             existing equipment from operating data. This latter is
                                   1LMTD2 des  1LMTD2 cond
                                                                             termed performance evaluation.
                                       1,680,000
                                                     17.7°F
                                  420,000  1,260,000

                                    38.8      15
                                                                                     Example 10-6. Heat Duty of a Condenser
                         For shells in series it is necessary to develop a weighted         with Liquid Subcooling
                       MTD correction factor, and a graphical technique is pre-
                       sented by Gulley. 59                                    The overhead condenser on a distillation column is to
                                                                             subcool the condensed vapors from the condensation tem-
                       Heat Balance                                          perature of 46.4°F down to 35°F. The specific heat of the
                                                                             liquid is 0.3 Btu/lb (°F), and the latent heat of vaporization
                         In heat exchanger design, the exchange of the heat  at 46.4°F is 265 Btu/lb. The vapor rate to the condenser is
                       between fluids is considered to be complete (i.e., 100%)  740.3 lb/hr. What is the total heat load on the condenser?
   101   102   103   104   105   106   107   108   109   110   111