Page 183 - Applied Process Design For Chemical And Petrochemical Plants Volume III
P. 183

66131_Ludwig_CH10E  5/30/2001 4:33 PM  Page 146










                       146                       Applied Process Design for Chemical and Petrochemical Plants

                                                                                                                  70
                       number of increments, 5—7, will produce results on the high  The general method as outlined by Kern has been sup-
                       side. In one case studied the use of 6 points compared to 17  plemented in the following discussion. The test of Revilock 96
                       points resulted in an area 36% too high. An important fac-  indicates the general applicability of the method.
                       tor in this analysis is the shape of the heat transfer curve.
                       Increments should be chosen smaller in the areas where the  1. The method is applicable only to gas-vapor mixtures
                       rate of change of heat load with temperature is the greatest  with the vapor at saturation. However, systems involving
                       (see Figures 10-87 and 10-88).                            superheated mixtures and subcooling can be handled
                                              39
                         The work of Dmytryszyn indicates that the best agree-   as separate problems and added to the cooler-
                       ment between actual and calculated surface areas using the  condenser area requirements to form a complete unit.
                       Colburn-Hougen method, when tested with vapors outside a  2. Assume temperature increments of condensation from
                       single vertical tube, requires a graphical solution to calculate  the inlet temperature to the outlet. The increments
                       the heat transfer surface required to cool the incoming gas  should be smaller near the inlet as most of this heat
                       mixture to its dew point (area described 1, 2, 3, 4), Figure  load will be transferred at the higher temperature level.
                       10-89. The area (described as 1, 2, 3, 5, l) calculated for gas  The number of increments is a function of the desired
                       desuperheating is too large when determined by the usual  accuracy. However, as a rule, the minimum should be 4,
                       equations; likewise, calculations based on an overall con-  with 6 or more being preferred.
                       densing coefficient give results that are too low. 39   3. Calculate the gas cooling and condensing heat loads
                                                                                 for each increment separately and plot a curve repre-
                                                                                 senting the total heat load versus temperature.
                                                                               4. Assume an exchanger unit, establishing shell size, num-
                                                                                 ber of tubes, and number of passes. Because the esti-
                                                                                 mation of overall U values for this type of unit is much
                                                                                 more variable than for some of the other units, a rough
                                                                                                                          2
                                                                                 value may be taken between 30 and 60 Btu/hr (ft ) (°F)
                                                                                 as a start (see Table 10-15). The actual weighted  t will
                                                                                 be somewhat larger than an LMTD value; however, this
                                                                                 is difficult to approximate without a trial or two or
                                                                                 unless a condensate film temperature, t f  , can be esti-
                                                                                 mated for the inlet and outlet conditions of several
                                                                                 intervals. An average difference value of these t f values
                                                                                 and the inlet gas temperature to the interval will give a
                                                                                 reasonable estimating value for the temperature differ-
                                                                                 ence in determining the estimating area, A.



                       Figure 10-87. Plot of exchanger surface area without fouling for gas-
                       cooling-condensing section only, Example 10-15.






















                       Figure 10-88. Heat load curve for condensing presence of noncon-  Figure 10-89. Graphical evaluation of gas desuperheating area for a
                       densables for Example 10-15.                          noncondensable-condensable mixture.
   178   179   180   181   182   183   184   185   186   187   188