Page 240 - Applied Process Design For Chemical And Petrochemical Plants Volume III
P. 240

66131_Ludwig_CH10G  5/30/2001 4:37 PM  Page 203










                                                                    Heat Transfer                                          203

                                         Table 10-34
                        Vertical Thermosiphon Reboiler Comparison: Effect
                           of Pressure Drop and Pipe Size on Selection

                                      3 / 4 In.    1 In.    1 In.    1 In.
                                        4 Ft     6 Ft    6 Ft    6 Ft
                     Tubes:             Long    Long    Long     Long
                     No. tubes         143      50       66      66
                     Inlet pipe size, in.  6     6        4       6
                     Outlet pipe size, in.  8    8        6       8
                     Shell I.D., in.    15.25   12       13.25   13.25
                     Recirc. ratio      42      40.5     42.1    55.7
                      P tubes, psi       0.97    1.55     1.03    1.31
                      P inlet pipe, psi  0.084   0.0789   0.41    0.137
                      P outlet pipe, psi  0.085  0.0824   0.251   0.111
                      P expansion, psi   0.00097  0.00209  0.00118  0.0011
                     U (calc.)          79.3    92.6     82.4    94.0
                     U (used)           66.1    92.4     70.0    70.0      Figure 10-121. Hajek correlation thermosiphon reboilers overall coef-
                                       105.3    75.2     99.3    99.3      ficients at maximum flux. (Used by permission: Hajek, J. D. Private
                     Area, ft 2
                                                                           communication. Deceased.)



                     Simplified Hajek Method—Vertical Thermosiphon
                     Reboiler

                       Although various correlations exist within thermosiphon
                     reboiler data, each seems to have some limitation. The
                                    60
                     method of Hajek recommended here has shown excellent
                     correlation above and below atmospheric pressure. Operat-
                     ing data for water, acetic acid, benzene, styrene, ethyl ben-
                     zene, and styrene-ethyl benzene mixtures agree well with
                     predicted data at intermediate operating heat fluxes. Back
                     calculated fouling factors were about 0.001 for the inside
                                               75
                     surface. The data of Lee, et al., is also included in the cor-
                     relation. Data presented are good for vertical natural circu-
                     lation thermosiphon reboilers with 1-in. 14 BWG Admiralty
                     tubes 4–10 ft in length. Data are based on 10 ft long tubes.
                     Maximum flux for the shorter tubes is greater. For 4, 6, and  Figure 10-122.  Overall   T at maximum flux; vertical thermosiphon
                     8 ft tubes, add 17%, 9%, and 4%, respectively. Do not adjust  reboilers. (Used by permission: Hajek, J. D. Private communication.
                     intermediate flux values below the maximum flux. Column  Deceased.)
                     liquid level must be at the top tubesheet.              Inlet nozzles should be sized for 2.5 gpm liquid per tube
                       Design for no more than 90% of calculated maximum   with the inlet line pressure drop not to exceed 1.5 psi per
                     flux when using full shell diameter top outlet elbows. When  100 equivalent ft of inlet piping for total gpm. Nozzles may,
                     using top-tee type side outlet vapor nozzles, use 76% and  in all cases, come into the side of the bottom channel.
                     60% of the calculated maximum flux for organics and inor-  The design method is illustrated in Example 10-22 and
                     ganics, respectively.                                 uses Figures 10-121, 10-122, 10-123, and 10-124.
                       Full shell diameter top outlet vapor nozzles are recom-
                     mended. Top-tee outlet vapor nozzles usually cause the       General Guides for Vertical Thermosiphon
                     reboiler to fail before maximum flux is reached. If the latter          Reboilers Design
                     is used, the vapor nozzle should be a minimum of two-thirds
                     the shell diameter.                                     Nucleate vaporization rates usually run 15–40% (but can
                       For 90° elbows off of top vapor outlet channels, the area  be as low as 2–10%) per pass through the unit for organic
                     of nozzle for flow must be minimum of 1.25   the flow area  materials, averaging about 25–28% for many typical condi-
                     (net) of all tubes.                                   tions. Aqueous solutions range from a low of 5% to 25–30%.
   235   236   237   238   239   240   241   242   243   244   245