Page 241 - Applied Process Design For Chemical And Petrochemical Plants Volume III
P. 241

66131_Ludwig_CH10G  5/30/2001 4:37 PM  Page 204










                       204                       Applied Process Design for Chemical and Petrochemical Plants

                                                                               The best designs provide for the percentage vaporization
                                                                             per pass to have been completed by the time the fluid mixture
                                                                             reaches the upper end of the tube and the mixture is leaving
                                                                             to enter the bottom chamber of the distillation column. In
                                                                             order to assist in accomplishing this, the initial reboiler eleva-
                                                                             tion should be set to have the top tubesheet at the same level
                                                                             as the liquid in the column bottom section. A liquid-level con-
                                                                             trol adjustment capability to raise or lower this bottoms level
                                                                             must exist to optimize the recirculation. Sometimes, the level
                                                                             in the bottom of the column may need to be 25–30% of the
                                                                             reboiler tube length above the elevation of the tubesheet.
                                                                             Therefore, the vapor nozzle return from the reboiler must
                                                                             enter at sufficient elevation to allow for this possibility.
                                                                               Velocities of liquid entering the tubes should be in the
                                                                             range:
                       Figure 10-123.  Vertical thermosiphon reboilers, U T versus   T for
                       clean and fouled conditions. (Used by permission: Hajek, J. D. Private  1–4.5 ft/sec when operating in atmospheric pressure
                       communication. Deceased.)                               and above.
                                                                                 0.4–1.0 ft/sec when operating in a vacuum.

                                                                               A full opening valve or variable orifice should be able to
                                                                             restrict flows of liquid into the bottom of the reboiler so that
                                                                             the instability in the liquid in the column will not be directly
                                                                             introduced into the inlet of the reboiler. Generally, the liquid
                                                                             inlet nozzle size should be about 50% in the inlet tube flow
                                                                             cross-section area. A large line is sometimes used, but a restrict-
                                                                             ing provision should be provided to to stabilize operations.

                                                                                    Example 10-22. Hajek’s Method—Vertical
                                                                                            Thermosiphon Reboiler

                                                                               See Figure 10-125.
                                                                               A fractionator stripping light ends from water is designed
                                                                             to operate at 80% of tray flooding. The heat load is
                                                                             4,000,000 Btu/hr. Design the reboiler for full tower capacity
                                                                             or 5,000,000 Btu/hr. A base pressure of 50 psig is required to
                                                                             condense the overhead vapor with cooling water. Steam
                       Figure 10-124.  Vertical thermosiphon reboilers with a slope of log  pressure downstream of the control valve can drop to 200
                       U T/log T for determination of  T at points below maximum flux.  psig. Use 6-ft long Admiralty tubes, 1 in. O.D. by 14 BWG on
                       Note: n   slope. (Used by permission: Hajek, J. D. Private communi-  1
                       cation. Deceased.)                                    1  / 4 -in. triangular pitch. Inside and outside fouling resis-
                                                                             tances are 0.001 and 0.0005, respectively.

                                                                             Physical data required
                                                                                   L   6 ft tube length
                         The temperature difference between the exiting vapor-      L   57.4 lb/ft , liquid density
                                                                                              3
                       liquid mixture and the inlet shell-side steam or hot fluid  l v   911.8 Btu/lb, heat of vaporization based on vapor to
                       should not exceed 75–82°F, primarily due to fouling prob-      bottom tray
                       lems and possible conversion in the tube to inefficient film  P   64.7 psia, tower base vapor space pressure
                       boiling in the upper section of the tubes.                 P c   3,206 psia, critical pressure
                         Frequently used tubes in many vertical thermosiphons are
                       8 ft long, with 12 ft or 14 ft being maximums. The popular  Variables to be determined
                              1
                       size is 1  / 4 in. O.D., with 1 in. being used sometimes. Sizes  U   overall heat transfer coefficient, Btu/hr (ft )(°F)
                                                                                                                       2
                       up to 2 in. O.D. are certainly acceptable, depending on the   T   over-all temperature difference, °F
                       design criteria. Short tubes of 4 and 6 ft are used for special  n   slope   log U T/log T
                       applications, including vacuum conditions.                 P R   P/Pc   reduced pressure
   236   237   238   239   240   241   242   243   244   245   246