Standby power batteries  50R
    Table 50.5  Chloride Motive Power range of motive power batteries in hard rubber containers
    Overall height over   Type      Capacity at 30°C (Ah)   Cell dimensions (mm)   Filled
    standard terminal                                                            cell weight
     connectors (mm)              5h      6h       8h       Length     Width       (kg)
         245          BKF27A      247     255     267       224         160         20.6
                      BKF29A      266     274     287       240         160         22.0
                      BKF31A      285     294     308       255         160         23.5
         289          XVF27A      338     348     365       224         160         25.4
                      XVF39A      494     508     534       319         160         38.7
         352          IMF27A      475     489     512       224         160         32.8
                      IMF41A      730     752     788       335         160         49.5
         430          ILF27A      61 1    629     660       224         160         40.9
                      ILF4 1 A    940     968     1016      335         160         62.4
         483          TLF27A      702     723     758       224         160         45.8
                      TLF4lA     1080    1112     1166      335         160         70.4
         543          THF27A      819     844     884       224         160         52.5
                      THF4 1A    1260    1298     1360      335         160         79.2
         740          MTF9        488     503     527        81        222          35.4
                      MTF37      2196    2263     2372      310        227         153.8
         363          WAF5A       110     113     119        47        200           8.7
         428          WBF5A       140     144     151        47        200          10.2
         498          WCF5A       160     165     172        47        200          11.9
         578          WEF5A       200     206     216        47        200          14.2
































    Figure 50.1  Motive power Battoper automatic topping-up device   Figure 50.2  The  Chloride  Motive  Power  Battoper  automatic
    (Courtesy  of Chloride Batteries)           topping-up device in use (Courtesy of Chloride Batteries)

                                                  A  large  percentage  of  EHT  switchgear is  battery
      In either case a standby battery of  proven reliabil-   operated. Here  again  the  requirement  is  for  a  good
    ity  and maximum compactness is required,  which  is   high-rate discharge characteristic, since the switchgear
    capable of  supplying a  high  discharge current for  a   closing  solenoids  take  a  high  current  for  a  very
    comparatively short period.                 short time.