Table 50.7 High-performance Piante-type lead-acid standby power storage batteries available from Chloride Industrial Batteries
Final Cell type
voltage
(V) YHP 11 YHP 13 YHP 15 YHP 17 YHP 19 YHP 21 YHP 23 YHP 25 YHP 27 YHP 29 YHP 31 YHP 33 YHP 35 YHP 37 YHP 39 YHP 41
Capacity*
at 15°C (Ah)
when discharged in
10h 1.85 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
3h 1.80 406 487 568 649 730 811 892 973 1054 1135 1217 1298 1379 1460 1541 1622
Ih 1.75 300 360 420 480 540 600 660 720 780 840 900 960 1020 1080 1140 1200
Capacity"
at 25°C (Ah)
when discharged in
10h 1.85 536 643 750 858 965 1072 1179 1286 1394 1501 1608 1715 1822 1930 2037 2144
3h 1.80 438 526 614 702 789 877 965 1052 1140 1228 1315 1403 1491 1578 1666 1754
lh 1.75 327 392 458 523 589 654 719 785 850 915 981 1046 1112 1177 1242 1308
Charge current (A)
Starting - 70 84 98 112 126 140 154 168 182 196 210 224 238 252 266 280
Finishing 2.7 35 42 49 56 63 70 77 84 91 98 105 112 119 126 133 140
Weight of cell
complete (kg)
Filled 95.2 106.2 133.5 144.5 155.5 179.3 190.4 218.0 220.0 240.1 268.3 279.2 290.2 318.2 329.2 340.2
Acid only, relative
density 1.210 32.2 30.6 45.3 43.7 42.1 53.3 51.8 66.8 65.2 63.7 79.3 77.6 76.0 91.4 89.8 88.2
Approx. quantity of 2
acid, relative density 3
Q
1.210 (litres) 27.1 25.7 38.1 36.7 35.4 44.8 43.5 56.1 54.8 53.5 66.6 65.2 63.9 76.8 75.5 74.1 3
__ ___._ U
* Larger capacitieh can he obtained by connecling cells in parallel. Smaller capacities are available in the YAP range (15-75 Ah) and YCP range (100-425 Ah)
4