Page 523 - Battery Reference Book
P. 523

Table 50.9  High-performance flat-plate vented lead-acid  standby power batteries available from Chloride Industrial Batteries







               Capacity* at 20°C (Ah)
               to BS 440 final voltage                                                                                                 W
                10 h                 1.85   16   32   48   64   80   96   128   160   120   180   240   300   360   420   480   540   600   $
                                                                                                                                460
                3h                   I .80   12.3   24.6   36.9   40.2   61.5   73.8   98.4   123   92   138   184   230   276   322   368   414   310  3
                lh                   1.75   8.4   16.8   25.2   33.6   42   50.4   67.2   84   62   93   124   155   186   217   248   279
               Capacity* at 20°C (A hj
               emergency lighting ratings to
               final voltage 85% ol' nominal
                3h                   1.70   13.6   27.2   40.8   54.4   68   81.6  108.8  136   102   153   204   255   306   357   408   459   510
                2h                   1.70   12   24   36   4x   60   72   96   120   90   135   180   225   270   315   360   405   450
                lh                   1.70   8.8   17.6   26.4   35.2   44   52.8   70.4   88   66   99   132   165   198   231   264   297   330
               Capacity* at 25°C (Ah)
                8h                   1.75   17   35   51   68   85   102   136   170   128   192   256   320   384   448   512   576   640
                3h                   I .75   13.2   26.4   39.6   52.8   66   79.2  105.6  132   99   148.5   198   247.5   297   346.5   396   445.5   495
                Ih                   1.75   8.7   17.4   26.1   34.8   43.5   52.2   69.6   87   64   96   128   160   192   224   256   288   320
               Charge current (A)
                Starting              -    2    4    7    9    11   13   18   22   17    25   34    42    50    59   67    76    86
                Finishing            2.70   1   2    3    4    5    6    9    11    8    12   17    21    25    29   33    38    42
               Weight of  cell completc (kgj
                Filled                     3.2   3.9   5.7   6.5   9.5   10.4   12.2   13.6   15.4   17.9   22.9   28.0   33.3   35.6   41.4   49.2   52.0
                Acid only, relative
                dcnsity 1.240*             1.3   1.2   2.0   2.0   3.6   3.5   3.5   4.0   5.8   5.2   7.3   9.0   10.7   10.1   12.2   16.3   16.0
               Approx. quantity of
               acid, relative density
               1.2401 (litres)             1.1   I .o   1.6   I .5   2.8   2.8   2.7   3.1   4.68   4.19   5.89   7.26   8.63   8.15   9.83   13.15   12.90
               External dimensions of  box (mm)
                Lengtht                    76   76   114   114   190   190   190   228   134   134   172   210   248   248   286   362   362
                Width                     133   133   133   133   133   133   133   133   203   203   203   203   203   203   203   203   203
                Height                    212   212   212   212   212   212   212   212   349   349   349   349   349   349   349   349   349
               Overall height of  cell (mm)   253   253   253   253   253   253   253   253   423   423   423   423   423   423   423   423   423
               * Larger capacitics can be obtaincd by coniiecting cells in parallel. Capacity levels applicable after five dischargdcharge cycles
               t The length of a box or cell is measured at right angles to the plates. The width is measured parallel to the plates
               t  1.270 for FAP rangc
   518   519   520   521   522   523   524   525   526   527   528