Table 50.6 High-performance Plante-type lead-acid standby power batteries available from Chloride Industrial Batteries e.
a
VI m
Final Cell type 0
voltage 2
(V) YAP5 YAP9 YAP13 YAP17 YAP21 YCP9 YCP 11 YCP13 YCP17 YCP2I YCP2.5 YCP27 YCP29 YCP.33 YCP35
3
Capacity* at 15°C (Ah) when
discharged in 8
10h 1.85 15 30 45 60 75 100 125 150 200 250 300 325 350 400 425 3.
3h 1.80 12 24 36 47.5 60 80 99 119 159 199 239 258 278 318 338
Ih I .75 9 18 27 36 45 60 75 90 120 150 180 195 210 240 255
Capacity* at 25°C (Ah) when
discharged in
10h 1.85 16 32 48 64 80 107 134 161 214 268 322 348 375 429 456
3h 1.80 13 26 38.5 52 64 86 107 129 172 215 258 279 301 344 365
1h 1.75 9.8 19.5 29.5 39 49 65 82 98 131 163 196 212 229 262 278
Charge current (A)
Starting - 2 4 6 8 10 14 17 20 28 34 42 46 48 56 60
Finishing 2.70 1 2 3 4 5 7 8.5 10 14 17 21 23 23 28 30
Weight of cell complete (kg)
Filled 3.8 6.3 10.0 11.45 13.6 18.6 22.2 24.9 30.6 36.9 43.4 52.6 54.4 58.4 60.3
Acid only (relative density
1.210) 1.16 1.89 3.4 3.25 3.8 5.5 7.5 7.2 8.7 10.4 12.1 16.6 16.2 15.5 15.1
Approx. quantity of acid,
relative density 1.210 (litres) 0.96 1.56 2.83 2.68 3.16 4.5 6.2 5.9 7.2 8.6 10 13.7 13.4 12.8 12.5
External dimensions of
box (mm)
Lengtht 76 114 190 190 228 134 172 172 210 48 86 362 362 362 62
Width 133 133 133 133 133 203 203 203 203 203 203 203 203 203 203
Height 212 212 212 212 212 349 349 349 349 349 349 349 349 349 349
Overall height of cell (mm) 260 260 260 260 260 423 423 423 423 423 423 423 423 423 423
* Larger capacity enclosed Plant6 cells are available in the YHP range (500-2000Ah)
The lcngth of a box or cell is measured at right angles to the plates. The width is measured parallel to the plates