Page 331 - Boiler_Operators_Handbook,_Second_Edition
P. 331

316                                                                               Boiler Operator’s Handbook


               air blowers. I don’t like them because it’s very difficult  matching drill bits. That’s very important to do before
               to  balance the  fuel distribution  to get  them  to  burn  closing a burner when refractory work is done because
               cleanly and efficiently. The few I’ve encountered can’t  there’s a tendency of masons to leave smears of refrac-
               seem to fire without a considerable amount of CO.    tory on and in the openings of gas rings.
                    Atmospheric burners are only used on small boil-     The gas ring is usually bolted to the boiler front
               ers, hot air furnaces, and service water heaters for the  plate, that thick piece of steel that seals the front of the
               most  part  because  they  are  normally  fixed  fired  and  boiler, provides support or is integrated with support
               have very little control of overall excess air. I’ve seen  of the refractory front wall. The front plate supports the
               large boilers, as big as 150 horsepower, with atmospher-  burner throat to keep it centered, and provides means of
               ic burners and have shuddered at the thought of what it  attaching the burner or windbox. If the gas ring or the
               costs to operate them. If they serve a constant load for  boiler front plate is distorted then air leakage around the
               which they’re well matched then there’s some sense in  gas ring at different points can produce very unstable
               their application but in any service with a varying load  firing conditions. The condition of the gas ring and
               the off cycle losses are very large.                 clearances (if any) between the gas ring and boiler front
                    Controlling those losses with dampers that shut off   plate should also be checked annually.
               air flow through the boiler when it’s not firing can pro-     If you find a warped front plate or other problems
               vide significant reductions in those losses. The dampers  with irregular air spaces around a gas ring you can
               have to be proved open before the boiler fires. Modern  plug them with ceramic fiber rope. Always put the rope
               high efficiency heating equipment with pulse combustion  on the windbox side and be certain it’s large enough
               or power burners should replace most of that equipment  it won’t blow through. It’s very embarrassing to have
               in the next few years once gas prices rise again. I’ve been  someone ask you what that thing is fluttering in the fire.
               able to show a boiler with a power burner can pay for it-     Gas rings can fail. Failure of adjustments of firing
               self over an atmospheric fired unit in less than a year. Any  rate, like linkage slipping, and other contributions can
               medium to large boiler should have a power burner and  produce situations where the heat of the fire is shifted
               unless one isn’t available, it should be modulating.  into the throat where it can overheat the gas ring to cre-
                    Fuel gas can be introduced into a power burner via  ate cracks in it. Any cracked gas ring should be replaced
               a gas ring, spuds or a gas gun. A gas ring is a piece of  before the boiler fires gas.
               pipe, fabricated steel or a casting surrounding the burn-     There was a time when we attempted to deliver
               er right at the boiler front plate with holes drilled in it  the fuel gas into the flame in the furnace as uniformly
               to distribute the gas evenly around the outside diameter  as possible to ensure complete mixing and permit low
               of the throat. Some gas rings are fitted with spuds while  excess air firing. The discovery of NO  as a problem has
                                                                                                      x
               other burners have spuds at the end of pipes which de-  resulted in irregular gas delivery schemes, usually us-
               liver the gas from the front of the burner or a gas ring  ing spuds (Figure 10-50) installed with pairs facing each
               located outside the front of the burner.             other to produce alternating fuel rich and lean zones in
                    Spuds are high temperature metal nozzles drilled  the burner. See the section on emissions for an explana-
               with holes to admit the gas into the passing air stream.  tion of why.
               A gas gun consists of a pipe central to the burner with a     The fuel gas piping has to penetrate the windbox
               closed end drilled to admit the gas very similar to an oil  or burner to deliver the gas to the gas ring. There was
               burner. Some gas guns consist of two concentric pipes  a time when we used a flanged connection on the gas
               that permit insertion of an oil gun down the center of  ring to permit disassembly but it also placed a poten-
               them. The arrangement, distribution and mix of holes  tial point for leakage of gas inside the burner windbox.
               drilled in gas rings, spuds and guns varies with manu-  There it could light off producing heat in a windbox
               facturer and in many instances is customized during  that wasn’t designed to absorb that heat. There are also
               startup to achieve smooth stable combustion.         many variations in design of packing glands and other
                    Retaining data on the drilling of your gas burner is  means of sealing the gas piping where it penetrates the
               essential because your information may be the only ac-  windbox. If you ever have problems with air leakage at
               curate copy around; it’s not unusual for a manufacturer  the gas line entrance the best solution is welding it to
               to fail to update the records for changes made by the  the windbox. Normally the windbox is flat and flexible
               service technician. One element of your annual boiler in-  enough at the gas line entrance that thermal expansion
               spection should be checking the diameter of the holes in  is accommodated by the windbox flexing. If you have
               the gas ring, nozzle, spuds or combination thereof with  problems with leaking piping joints inside the windbox