Page 106 - Boiler plant and distribution system optimization manual
P. 106

Boiler Tuneup                                                                                      91



                                                                    •    Make sure that the burner diffuser (impeller)
                                                                         is not damaged, and is properly located with
                                                                         respect to the oil gun tip.

                                                                    •    Check to see that the oil gun is positioned
                                                                         properly within the burner throat, and the
                                                                         throat refractory is in good condition.


                                                                    gas burners
                                                                    •    Be sure that filters and moisture traps are
                                                                         in place, clean and, operating properly to
                                                                         prevent gas orifice plugging. Inspect gas-
                                                                         injection orifices and verify that all passages
                                                                         are unobstructed.

                                                                    •    Look for any burned off or missing burner
                                                                         parts. Confirm location and orientation of
                                                                         all parts. (Viewing ports are very helpful to
                                                                         identify faulty flame patterns or other prob-
                                                                         lems)

                                                                    Pulverized-coal burners
                Figure 9.2—Boiler exhaust temperature above tem-    •    Verify that fuel and air components, pul-
                perature of water-steam temperature in boiler.           verizes, feeders, primary and tempering-air
                                                                         dampers etc are all working properly.

                •    Verify proper flame pattern through the        •    Clear coal pipes of any coal and coke depos-
                     viewing ports located at the sides and back         its.
                     of the boiler, if installed.
                                                                    •    Check burner parts for any signs of excessive
                •    Inspect burners for warping or overheating,         erosion or burn-off.
                     coke and gum deposits. Clean or replace
                     parts as appropriate.                          Spreader-stoker firing
                                                                    •    Check grates for wear. Check the stokers and
                •    Inspect oil tip passages and orifices for wear
                                                                         the cylinder-reinjection system for proper
                     and scratches or other marks. Use proper
                                                                         operation.
                     size drill or machine gages for testing.
                                                                    •    Confirm the proper positioning of all air-pro-
                •    Verify proper oil pressure and temperature
                                                                         portioning dampers.
                     at the burner. This may include resetting the
                                                                    •    Verify proper coal sizing.
                     fuel oil heater to the grade of oil presently
                     being fired, calibrating gages and instru-
                                                                    Combustion controls
                     ments and resetting pressures to manufac-
                                                                    •    Be sure that all safety interlocks and boiler
                     tures values or values indicated in engineer-
                                                                         trip circuits operate.
                     ing records. If changes are made, careful
                     observation of actual effects they produce is   •   See that all system gages are calibrated and
                     important in the case a problem develops.           functioning.
                •    Verify proper atomizing-steam pressure.        •    Eliminate play in all control linkages and
                     Also, be aware a defective steam trap may           air dampers. Also check to see if there is
                     introduce unwanted water into the flame             accurate repeatability when load points are
                     zone.                                               approached from different directions.
   101   102   103   104   105   106   107   108   109   110   111