164                                                 Boiler Plant and Distribution System Optimization Manual


                Description                                         Advantages/Disadvantages
                     Installing pressure reducing valves near the        It is a more complex system to manage but
                point-of-use can reduce flash steam losses. Also,   produces electric power much cheaper than com-
                high pressure steam has a higher temperature,       mercial power.
                lower specific volume and is economical to dis-
                tribute through steam mains requiring smaller
                sized piping. As a general rule, steam is most eco-  13.  HAVE A STEAM SYSTEM SURVEY
                nomically distributed at high pressure and if re-        DONE BY A PROFESSIONAL
                duced to the lowest pressure that will satisfy the       CONTRACTOR
                temperature requirements at the point-of-use, the
                least amount of energy will be lost.                     Steam system surveys can be quite informa-
                     Advantages come with lowering steam pres-      tive and useful but requiring special skills, judg-
                sure;  a  600  psig  system  will  have  a  30%  flash   ment and background. Their usual product is a
                steam rate, at 175 psi this reduces to a 17% flash   map  of  your  steam  system  with  all  traps  iden-
                and at 50 psi its 4%. This represents a consider-   tified  as  to  type  and  manufacturer,  quite  useful
                able amount of energy because every pound of        for ordering parts and replacements. The traps
                steam  flashed  contains  about  1,100  Btus  where   are  given  identification  tags  and  you  also  get  a
                the condensate contains only 180 Btus per pound     condition report on each trap with misapplication
                a difference in energy levels of about 6.           information and such. It’s a good way to identify
                                                                    any problems with your steam system as a start to
                Advantages/Disadvantages                            putting it right and a successful energy conserva-
                     The cost of installing and maintaining pres-   tion program.
                sure reducing valves and possible replacement of
                steam traps will have to be balanced against pre-   Advantages/Disadvantages
                dicted savings.                                          It might seem a little expensive or unusual
                                                                    but it is a good way to find out exactly what is
                                                                    going  on  with  your  steam  distribution  system.
                12.  UTILIzE BACKPRESSURE TURBINE                   Good reports and successful energy savings are
                     FOR STEAM PRESSURE REDUCTION                   the usual case concerning these special surveys.


                Description
                     The use of turbogenerators as an option for    14.  INSTALL PRESSURE PUMP RETURNS
                reducing steam pressures in large plants instead         ELIMINATING ELECTRIC PUMPS
                of pressure reducing valves is an efficient way to
                generate electricity. It starts with relatively high      Electrical  pumps  have  a  number  of  draw-
                pressure steam boilers on the high pressure end of   backs.  Being  electrical  in  a  wet  environment
                the steam system. The steam pressure is reduced     sometimes gets unhealthy for the electrical end
                to intermediate and low pressure steam systems      of  things.  They  have  centrifugal  impellers  that
                through the turbines before it enters the plant’s   can form a partial vacuum at the water inlet with
                steam distribution system. This is a very efficient   the water near the boiling point. This can cause
                way to generate electricity at 80% efficiency rath-  steam flashing and the loss of suction and effec-
                er than efficiencies in the 33% range by electrical   tiveness and of course there is the electrical load
                generating  plants  which  have  no  way  to  utilize   and the need to have electricians prowling your
                their turbine exhausts. The usual design is 50      steam system’s tunnels vaults and confined spac-
                KW and up with a minimum steam flow of 3,000        es checking on things and making repairs.
                pounds per hour.                                         The industry has come up with an alterna-
                                                                    tive  pump  (Figure  10.60)  without  these  draw-