34                                                  Boiler Plant and Distribution System Optimization Manual























































                                   Figure 3.3—Efficiency  change  for  each  10°F  change  in  stack
                                   temperature for various levels of excess air.






                IMPROVING RADIANT HEAT TRANSFER                     FLAME TEMPERATURE

                     The radiation section or that section of the        Table 3.5 shows that as the excess air is re-
                boiler exposed to direct radiation from combus-     duced,  flame  temperatures  rise.  Combustion
                tion, is the most effective heat transfer zone of a   flame temperatures are very complex to analyze
                boiler.  Figure  3.4  shows  that  8%  of  the  heat  ex-  and this chart should be treated only as an ap-
                change surface of a boiler is absorbing about 48%   proximation. It can be seen in Table 3.5, at 0%
                of the energy from combustion. The convection       excess air, the flame temperature is about 3,400 F
                section,  which  comprises  34%  of  the  heat  ex-  [1,871C] for natural gas and at 100% excess air this
                change surface only absorbs about 20% of the        temperature drops to about 2,000 F [1,093C]. For
                heat of combustion.                                 number 6 oil these numbers are 4,000 F [2,204C]