CHAPTER 6                       APPLICATIONS OF BRIDGE DESIGN AND RATING METHODS            261



        6.7  EXAMPLE OF LOAD RESISTANCE FACTOR RATING (LRFR)

        6.7.1  Analysis Procedure for a Two-Girder Steel Bridge
            The following steps are provided for ready reference. Prior to developing a software or for
        solving the equations using hand calculations, equations need to be checked against the latest

        version of applicable AASHTO LRFD Specifications or LRFR Manual.

        •   Refer to AASHTO Manual for Condition Evaluation of Bridges Example A8.
            Geometry, materials, traffi c data:
            LL 3 HL-93 (HS-25 truck and lane)
            Span 3 100 ft
            fc1 3 2.5 ksi
            Fy 3 30 ksi
            ADTT 3 500
            Skew 3 0 deg.
            Spacing of fl oor beams 3 10 ft

            Overlay thickness 3 1.5 in

        •   For equilibrium, $ horizontal resisting forces above NA 3 $ horizontal resisting forces
            below NA
            Force in top fl ange 3 P  3 F  b  t 3 Force in bottom fl ange P
                                c    yc  c c                     t
            Force in web 3 P 3 P
                           wc   wt
            – a 3 D/2 (LRFD Appendix A 6.1, Case 1)

            d  3 d
             c    t
            For an economical design, when shear and deflection criteria are met:

            Maximumpositive moment 3 Maximum negative moment.

            For floor beams, cantilever overhangs at each end are provided.

            Plastic moment of resistance (M ) 3 Force in top fl ange 8 Distance to NA 4 Force in bot-
                                       p
            tom fl ange 8 Distance to NA 4 Force in web x Distance to NA
             3 (P 8 d 4 P 8 d ) 4 P 8 [(a) 4 (D 6 a) ] / 2D
                                                   – 2
                                        – 2
                 c   c    t   t    w
        •   Check for compactness:

            Positive moment compression flange is fully in contact with the deck and is adequately
            braced.
            Assume section as compact (LRFD Section 6.6.9.3).
            Negative moment section: Lateral bracing L   (r  E/F ) [0.124 6 0.0759 (M  /M )]
                                                 b    y   yc                  1  p
            (LRFD Section 6.10.4.1.7)