Page 253 - Chemical engineering design
P. 253

229
                                          PIPING AND INSTRUMENTATION
                     4. Decide and show those ancillary instruments needed for the monitoring of the plant
                        operation by the operators; and for trouble-shooting and plant development. It is
                        well worthwhile including additional connections for instruments which may be
                        needed for future trouble-shooting and development, even if the instruments are not
                        installed permanently. This would include: extra thermowells, pressure tappings,
                        orifice flanges, and extra sample points.
                     5. Decide on the location of sample points.
                     6. Decide on the need for recorders and the location of the readout points, local or
                        control room. This step would be done in conjunction with steps 1 to 4.
                     7. Decide on the alarms and interlocks needed; this would be done in conjunction with
                        step 3 (see Chapter 9).


                                    5.8. TYPICAL CONTROL SYSTEMS
                   5.8.1. Level control
                   In any equipment where an interface exists between two phases (e.g. liquid vapour),
                   some means of maintaining the interface at the required level must be provided. This
                   may be incorporated in the design of the equipment, as is usually done for decanters,
                   or by automatic control of the flow from the equipment. Figure 5.16 shows a typical
                   arrangement for the level control at the base of a column. The control valve should be
                   placed on the discharge line from the pump.












                                               Figure 5.16.  Level control

                   5.8.2. Pressure control

                   Pressure control will be necessary for most systems handling vapour or gas. The method
                   of control will depend on the nature of the process. Typical schemes are shown in
                   Figures 5.17a, b, c, d (see p. 230). The scheme shown in Figure 5.17a would not be
                   used where the vented gas was toxic, or valuable. In these circumstances the vent should
                   be taken to a vent recovery system, such as a scrubber.

                   5.8.3. Flow control
                   Flow control is usually associated with inventory control in a storage tank or other
                   equipment. There must be a reservoir to take up the changes in flow-rate.
                     To provide flow control on a compressor or pump running at a fixed speed and
                   supplying a near constant volume output, a by-pass control would be used, as shown
                   in Figures 5.18a, b (see p. 231).
   248   249   250   251   252   253   254   255   256   257   258