BUILDING AND STRUCTURES FORMULAS        219

             PLATE GIRDERS IN BUILDINGS

             For greatest resistance to bending, as much of a plate girder cross section as
             practicable should be concentrated in the flanges, at the greatest distance from
             the neutral axis. This might require, however, a web so thin that the girder
             would fail by web buckling before it reached its bending capacity. To preclude
             this, the AISC specification limits h/t.
               For an unstiffened web, this ratio should not exceed

                                 h       14,000
                                                                  (9.44)
                                 t     F y (F y   16.5)

             where F   yield strength of compression flange, ksi (MPa).
                   y
               Larger values of h/t may be used, however, if the web is stiffened at appro-
             priate intervals.
               For this purpose, vertical angles may be fastened to the web or vertical plates
             welded to it. These transverse stiffeners are not required, though, when h/t is less
             than the value computed from the preceding equation or Table 9.4.
               With transverse stiffeners spaced not more than 1.5 times the girder depth
             apart, the web clear-depth/thickness ratio may be as large as

                                      h   2000
                                                                  (9.45)
                                      t    F y

               If, however, the web depth/thickness ratio h/t exceeds 760/  F b ,  where F ,
                                                                     b
             ksi (MPa), is the allowable bending stress in the compression flange that would
             ordinarily apply, this stress should be reduced to  F b   , given by the following
             equations:

                        F b    R PG R e F b                       (9.46)
                                        A w     h  760
                        R PG   1   0.0005                1.0      (9.47)
                                        A f  t   F b
                                12   (A w /A f )(3    )           (9.48)
                                               3
                         R e      12   2(A w /A f )    1.0


                      TABLE 9.4 Critical h/t for Plate Girders in Buildings
                                            14,000       2,000
                      F , ksi  (MPa)     2 F y (F y   16.5)  2 F y
                       y
                        36      (248)        322         333
                        50      (345)        243         283