Page 292 - Civil Engineering Formulas
P. 292

226                    CHAPTER NINE

           completely braced laterally, the allowable stress in the flanges is 0.66F , where
                                                               y
           F is the yield strength, ksi (MPa), of the steel. Assuming the steel to carry the
            y
           full dead load and the composite section to carry the live load, the maximum unit
           stress, ksi (MPa), in the steel is
                                  M D   M L
                              f s            0.66F y            (9.66)
                                  S s   S tr
           where M   dead-load moment, in kip (kN mm)
                  D
                 M   live-load moment, in kip (kN mm)
                  L
                                                  3
                                             3
                 S   section modulus of steel beam, in (mm )
                  s
                                                            3
                                                                3
                 S   section modulus of transformed composite section, in (mm )
                  tr
             An alternative, shortcut method is permitted by the AISC specification. It
           assumes that the steel beam carries both live and dead loads and compensates
           for this by permitting a higher stress in the steel:
                              f s    M D   M L    0.76F y       (9.67)
                                     S s
           Method 2 The steel beam is connected to the concrete slab by shear connectors.
           Design is based on ultimate load and is independent of the use of temporary
           shores to support the steel until the concrete hardens. The maximum stress in the
           bottom flange is
                                  M D   M L
                              f s           0.66F y             (9.68)
                                     S tr
             To obtain the transformed composite section, treat the concrete above the
           neutral axis as an equivalent steel area by dividing the concrete area by n, the
           ratio of modulus of elasticity of steel to that of the concrete. In determination of
           the transformed section, only a portion of the concrete slab over the beam may
           be considered effective in resisting compressive flexural stresses (positive-
           moment regions). The width of slab on either side of the beam centerline that
           may be considered effective should not exceed any of the following:
           1. One-eighth of the beam span between centers of supports
           2. Half the distance to the centerline of the adjacent beam
           3. The distance from beam centerline to edge of slab (Fig. 9.5)



           NUMBER OF CONNECTORS REQUIRED
           FOR BUILDING CONSTRUCTION

           The total number of connectors to resist V is computed from V /q, where q is
                                                          h
                                          h
           the allowable shear for one connector, kip (kN). Values of q for connectors in
           buildings are given in structural design guides.
             The required number of shear connectors may be spaced uniformly between
           the sections of maximum and zero moment. Shear connectors should have at