Page 451 - Civil Engineering Formulas
P. 451

STORMWATER, WASTEWATER, AND ENVIRONMENTAL PROTECTION  377

                     TABLE 13.2 Typical Dosing Rates for Trickling Filters
                                      /10 3         Dosing rate,
                     Organic loading lb BOD 5
                         3
                               2
                        ft  d (kg/m  d)           in./pass (cm/pass)
                         <25 (122.2)                  3 (7.6)
                          50 (244.3)                 6 (15.2)
                          75 (366.5)                 9 (22.9)
                         100 (488.7)                 12 (30.5)
                         150 (733.0)                 18 (45.7)
                         200 (977.4)                 24 (60.9)
                        (Wastewater Engineering: Treatment, Disposal, and Reuse, Metcalf
                     & Eddy, 3rd Ed, McGraw-Hill.)

             achieve uniform growth and sloughing, higher periodic dosing rates are
             required. The required dosing rate in inches per pass of distributor arm may be
             approximated using the following:
                                                   3
                                                     3
                       Dosing rate   (organic loading, lb/10 ft  d)(0.12)  (13.67)
               Typical dosing rates for trickling filters are listed in Table 13.2. To achieve
             the typical dosing rates, the speed of the rotary distributor can be controlled by
             (1) reversing the location of some of the existing orifices to the front of the dis-
             tributor arm, (2) adding reversed deflectors to the existing orifice discharges,
             and (3) by operating the rotary distributor with a variable speed drive.
               The rotational speed of the distributor is a function of the instantaneous dos-
             ing rate and may be determined using the following:
                                         1.6(Q T )
                                    n                            (13.68)
                                        (A)(DR)
             where  n   rotational speed of distribution (rpm)
                                                                   2
                  Q   total applied hydraulic loading rate (gal/min sq ft) (L/s m )
                   T
                      Q   Q
                           R
                                                                    2
                   Q   influent wastewater hydraulic loading rate (gal/min sq ft) (L/s m )
                                                                 2
                  Q   recycle flow hydraulic loading rate (gal/min sq ft) (L/s m ) Note:
                   R
                      recycle is assumed to be zero in this example.
                   A   number of arms in rotary distributor assembly
                 DR   dosing rate (in/pass of distributor arm)
             DESIGN OF AN ANAEROBIC DIGESTOR
             Anaerobic digestion is one of the oldest processes used for the stabilization of
             sludge. It involves the decomposition of organic and inorganic matter in the
             absence of molecular oxygen. The major applications of this process are in the
             stabilization of concentrated sludges produced from the treatment of wastewater.