Page 528 - Decision Making Applications in Modern Power Systems
P. 528

A reliable decision-making algorithm Chapter | 18  487



               TABLE 18.6 Test results and confusion matrix of wavelet packet energy
               and bagged decision tree-1 module for detection of system condition
               (no-fault, power swing).

               Case    Data          Predicted      Actual class   Accuracy
               study   segmented     class                         (%)
                                                0      1     2
                       (%)
               Case-1  90 10         0          2000               100
                                     1                 8820
                                     2                       1710
               Case-2  80 20         0          2000               100
                                     1                 8820
                                     2                       1710
               Case-3  70 30         0          2000               100
                                     1                 8820
                                     2                       1710
               Case-4  60 40         0          2000               100
                                     1                 8820
                                     2                       1710
               Case-5  50 50         0          2000               100
                                     1                 8820
                                     2                       1710




             18.5.2 Discrimination of power swing condition
             (stable and unstable)
             A stable PS is initiated by creating a fault in the adjacent line connected to the
             monitored bus and clearing the fault before the critical clearing time (CCT),
             whereas if the fault is cleared after the CCT then it will initiate unstable PS in
             the system. For instance, a three-phase to ground fault has been incepted at
             1.001 seconds on a single-circuit transmission line of 60 km length which is
             connected between NTPC and Sipat in Fig. 18.1 and the same has been
             cleared by tripping the circuit breakers of both the ends at 1.15 seconds, that
             is, fault clearing time is 7.5-cycles. In order to identify the state of the system
             during this stressed condition, that is, the PS is stable or unstable; WPE_BDT-
             2 module is tested, and the test results are demonstrated in Fig. 18.7.The
             three-phase current and voltages of the monitored double-circuit line are
   523   524   525   526   527   528   529   530   531   532   533