Page 523 - Decision Making Applications in Modern Power Systems
P. 523

482  Decision Making Applications in Modern Power Systems


            an extensive dataset is generated as exemplified in Table 18.2 18.5. To gen-
            erate an appropriate dataset for training/testing, extensive simulation studies
            have been performed by considering wide variation in operating conditions
            as follows: fault resistance ðR f Þ from 0 to 100 Ω, fault inception angle ðφ Þ
                                                                          f
            from 0 to 360 degrees, fault location ðL f Þ from 1 to 197 km, source imped-
            ance (Z) within 6 10%, power flow angle (δ) from 5 to 20 degrees.
               In this proposed protection scheme, exclusive datasets have been
            designed using an illustrative feature extraction technique, that is, WPE. To



              TABLE 18.2 Dataset generated for a wide range of variation in different
              parameters for wavelet packet energy and bagged decision tree-1
              modules.
              Parameter           Common shunt faults  Power swing (stable and
                                                       unstable)
              Fault on line       NTPC/KSTPS-to-Bhilai/  NTPC/KSTPS-to-Sipat
                                  Khedamara
              Fault clearing time (cycle)  5           2, 4, 6, 8, 10, 12, 14, 16, 18,
                                                       20
              Fault location ðL f Þ  198 km in steps of 2 km  60 km in steps of 3 km
              Fault inception angle ðφ f Þ  0, 90, and 270  0, 90, and 270
              (degrees)
              Fault resistance ðR f Þ (Ω)  0, 50, and 100  0, 50, and 100
              No. of fault cases  LG: 2646, LLG: 2646  LLLG:1710
                                  LL: 2646, LLL: 0882
              Total no. of cases  9020 5 8820 1 200 (no  1710
                                  fault)




              TABLE 18.3 Dataset generated for a wide range of variation in fault
              parameters for wavelet packet energy and bagged decision tree-2
              modules.

              Parameter                 Stable power swing  Unstable power swing
              Fault on line             NTPC/KSTPS-to-Sipat  NTPC/KSTPS-to-Sipat
              Fault clearing time (cycle)  2, 4, 6, 8     10, 12, 14, 16

              Fault location ðL f Þ     60 km in steps of 3 km  60 km in steps of 3 km
              Fault inception angle ðφ f Þ (degrees)  0, 90, and 270  0, 90, and 270
              Fault resistance ðR f Þ (Ω)  0              0
              Total no. of cases        LLLG: 228         LLLG: 228
   518   519   520   521   522   523   524   525   526   527   528