Page 194 - Design and Operation of Heat Exchangers and their Networks
P. 194

182   Design and operation of heat exchangers and their networks


          the mean vapor mass fraction (between inlet and outlet) in the test section.
          The correlation equation for R22 is given as
                             αd h,b            _ x 0:01  0:19  0:3
                                       ð
                       Nu ¼      ¼ 24:50:9+ _xÞ     Re    Pr         (4.216)
                                                       eq
                              λ l
             Longo (2010a) presented the heat transfer coefficients and the pressure
          drop measured during saturated vapor condensation of refrigerants
          R236fa, R134a (early reported by Longo and Gasparella, 2007 and Longo,
          2008) and R410A (early reported by Longo, 2009) inside a brazed plate heat
          exchanger with chevron angle of β¼65degrees. The experimental heat
          transfer coefficients have been compared against the classical Nusselt analysis
          for laminar film condensation on vertical surface (gravity controlled)

                                           2     3   1=4
                 αL                      gρ Δh v L
                                           l
            Nu ¼    ¼ ψNu Nusselt ¼ ψ0:943             Re eq   1600  (4.217)
                  λ l                     λ l μ ΔT
                                             l
          and the equation of Akers et al. (see Longo, 2010a) for forced convection
          condensation inside tube
                        ψ  ð L          ψ  ð L
                 αd h,b                            1=3  1=3
            Nu ¼      ¼     Nu x,Akers dx ¼  5:03Re eq  Pr l  dx Re eq   1700
                  λ l   L  0            L  0
                                                                     (4.218)

          where the equivalent Reynolds number is defined by Eq. (4.190). It is found
          that the deviations from the experimental data are acceptable. The deviation
          for gravity-controlled condensation and for forced convection condensation
          is about 10% and 20%, respectively. The condensation frictional pressure
          drop of R236fa, R134a, and R410A is expressed against the kinetic energy
          per unit volume of the refrigerant flow computed by the homogeneous
          model (see Eq. 4.192 for ρ m ):

                                  Δp f         KE=V
                                      ¼ 2:00                         (4.219)
                                 1 kPa        1J=m 3
          in which the kinetic energy per unit volume is defined as

                                             G 2
                                     KE=V ¼                          (4.220)
                                             2ρ m
          This implies that the condensation friction factor is a constant, f¼500d h,b /L.
          However, it seems to be suitable only for a special brazed plate heat
          exchanger. Longo (2010b) further presents the experimental results for
   189   190   191   192   193   194   195   196   197   198   199