Page 190 - Design and Operation of Heat Exchangers and their Networks
P. 190

178   Design and operation of heat exchangers and their networks


          4.2.4 Condensation in plate heat exchangers
          Condensation heat transfer in plate heat exchangers can be affected by geo-
          metrical parameters, plate surface characteristics, fluid characteristics, and
          operation conditions. Till now, there is no general correlation even for com-
          monly used plates with herringbone corrugation. Some correlations from
          different sources of the literature are listed as follows.
             Wang and Zhao (1993) presented the experimental results of water steam
          condensation in a plate condenser. The chevron angle β seems to be
          45degrees. They used the equivalent diameter as the characteristic length,
          but the definition was not declared. It might be the hydraulic diameter (from
          Eq. 4.103)

                                       d h,b ¼ 2b                    (4.184)
          where b is the plate spacing. The heat transfer coefficient for cooling water is
          given as

                                               0:4
                                 0:319Re 0:6425  Pr ,  Re   1000
                       α sp d h,b
                 Nu sp ¼     ¼                                       (4.185)
                                                0:4
                          λ      0:3489Re 0:6418 Pr ,Re > 1000
          The correlation equation for condensation is given as
                      αd h,b                0:983  0:33    0:248
                 Nu ¼      ¼ 0:00115 Re l =HÞ   Pr  ð ρ =ρ Þ         (4.186)
                                    ð
                                                  l   l  v
                       λ l
          where
                                Re l ¼ G 1  _x out Þd h,b =μ         (4.187)
                                       ð
                                                     l
           _ x out is the vapor mass fraction at the outlet of the plate condenser and H is a
          dimensionless parameter expressing the influence of subcooling of the
          condensate

                                          ð
                                       c p,l T s  T w Þ
                              H ¼                                    (4.188)
                                              ð
                                  Δh v +0:68c p,l T s  T w Þ
          In their experiments, _x out is ranged from 0 to 0.64.
             Yan et al. (1999) investigated the condensation heat transfer and pressure
          drop for R134a in a plate heat exchanger with a chevron angle of
          β¼60degrees. The exchanger consisted of three plates that formed two
          counterflow channels, downflow of the condensing R134a in one channel
          releasing heat to the cold upflow of water in the other channel. The char-
          acteristic length is d h,b defined by Eq. (4.184). The vapor mass fraction
          changes over the exchanger were not given. The correlation of the
   185   186   187   188   189   190   191   192   193   194   195