SHEAR WALLS                       7.87

         7.10.2 Seismic Design Categories
         Every structures in an occupancy category (Occupancy Category I, II, III, and IV) is
         assigned a SDC A through F based on consideration of following seismic design parameters
         (both must be considered simultaneously):
         1. Design, 5 percent damped, spectral acceleration parameter at short periods (0.2s), S
                                                                       DS
         2. Design, 5 percent damped, spectral acceleration parameter at 1-s period, S .
                                                                D1
           Values of S  and S  for various occupancy categories are listed in Tables 7.8 and 7.9;
                   DS    D1
         each building and structure is assigned more severe of the categories so determined.
                       TABLE 7.8  Seismic Design Category Based on
                       Design, 5 Percent Damped, Spectral Acceleration
                       Parameter at Short Periods, S  [7.13]
                                          DS
                                          Occupancy category
                                        I or II  III  IV
                           Value of S DS
                        S DS  < 0.167    A      A     A
                        0.167 ≤ S DS  < 0.33  B  B    C
                        0.33 ≤ S DS  < 0.5  C   C     D
                                         D      D     D
                        0.5 ≤ S DS

                     TABLE 7.9  Seismic Design Category Based on Design,
                     5 Percent Damped, Spectral Acceleration Parameter at a
                     Period of 1 s, S  [7.13]
                               D1
                                          Occupancy category
                                       I or II  III    IV
                         Value of S DS
                      S D1  < 0.067     A       A       A
                      0.067 ≤ S D1  < 0.133  B  B       C
                      0.133 ≤ S D1  < 0.20  C   C       D
                                        D       D       D
                      0.20 ≤ S D1
           The following exceptions apply to determination of seismic design category as deter-
         mined from Tables 7.8 and 7.9:

         1. Occupancy Category I, II, and III structures located where the mapped spectral accelera-

           tion parameter at 1-s period, S , is greater than or equal to 0.75 shall be assigned Seismic
                                1
           Design Category E.
         2. Occupancy Category IV structures located where the mapped spectral acceleration
           parameter at 1-s period, S , is equal to or greater than 0.75 (i.e., S  ≥ 0.75) shall be
                              1
                                                            1
           assigned Seismic Design Category F.
         3. Where S  is greater than 0.75, seismic design category is permitted to be determined based
                 1
           on considerations of only S  as listed in Table 7.8 where all of the following apply:
                              DS
           (a)  In each of the two orthogonal directions, the approximate fundamental period of the
              structure, T , is less than 0.8T .
                      a            s
           (b)  In each of the two orthogonal directions, the fundamental period of the structure
              used to calculate the story drift is less than T .
                                              s