Page 163 - Electrical Equipment Handbook _ Troubleshooting and Maintenance
P. 163

MAINTENANCE OF MOTORS

            8.18                       CHAPTER EIGHT

              Large and medium-size high-speed motors are the most susceptible to cracks in the
            cage winding. Large, low-speed motors driving high-inertia loads such as induced-draft
            (ID) and forced-draft (FD) boiler fans are also susceptible to this mode of failure. The bar
            extensions, short-circuit rings, and joints between these components are most susceptible
            to cracking. Cyclic mechanical stresses occurring during start-up lead to cracking by
            fatigue failure. These stresses are mainly produced by centrifugal forces and differential
            thermal expansion.
              The impedance around the rotor periphery becomes unbalanced by an open circuit in a
            squirrel-cage rotor winding. The amplitude of the stator current waveform will fluctuate as
            the magnetic field rotates relative to the rotor surface due to the open circuit. Figure 8.6
            illustrates this modulating effect.
              Fluctuations in shaft speed can also be caused by broken bars or short-circuit rings. In
            a healthy rotor, the torque varies sinusoidally at twice the slip frequency. When a bar is
            aligned with the center of the stator pole, it develops the maximum torque. Some sections
            of the cage winding will not develop any torque if the rotor has an open circuit. The shaft
            will slow down slightly twice during each slip cycle. The presence of an open circuit can
            be verified by measurement of these speed fluctuations.
              The two methods described below are used to detect open circuits in rotors. The stator
            current fluctuation test is performed on an operating and loaded motor. The normal
            power supply and driven equipment should be uncoupled before performing the manual
            rotation test.


            Stator Current Fluctuation Test

            This simple online technique has been used for many years. The current in one of the phases
            is monitored for fluctuations at twice the slip frequency. An ammeter is observed, or a cur-
            rent transformer output is monitored on a strip chart recorder or oscilloscope. The results
            should be interpreted by an experienced operator.


                                 2 
 slip
                                frequency





             Peak current amplitude  0  1   2            3           4  Time, s














            FIGURE 8.6 Two times slip frequency stator current modulation is induced by cage winding open circuit.



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   158   159   160   161   162   163   164   165   166   167   168